10.5 Inrush currents at power-on of main circuit and control circuit
POINT
For a servo amplifier of 600 W or less, the inrush current values can change
depending on frequency of turning on/off the power and ambient temperature.
Since large inrush currents flow in the power supplies, always use molded-case circuit breakers and
magnetic contactors. (Refer to section 11.10.)
When circuit protectors are used, it is recommended that the inertia delay type, which is not tripped by an
inrush current, be used.
(1) 200 V class
The following shows the inrush currents (reference data) that will flow when 240 V AC servo amplifier) is
applied at the power supply capacity of 2500 kVA and the wiring length of 1 m. Even when you use a 1-
phase 200 V AC power supply with MR-J4-10B(-RJ) to MR-J4-200B(-RJ), the inrush currents of the
main circuit power supply is the same.
Servo amplifier
Inrush currents (A
0-P
)
Main circuit power supply (L1/L2/L3)
Control circuit power supply (L11/L21)
MR-J4-10B(-RJ)
MR-J4-20B(-RJ)
MR-J4-40B(-RJ)
MR-J4-60B(-RJ)
30 A (attenuated to approx. 3 A in 20 ms)
20 A to 30 A
(attenuated to approx. 1 A in 20 ms)
MR-J4-70B(-RJ)
MR-J4-100B(-RJ)
34 A (attenuated to approx. 7 A in 20 ms)
MR-J4-200B(-RJ)
MR-J4-350B(-RJ)
113 A (attenuated to approx. 12 A in 20 ms)
MR-J4-500B(-RJ)
42 A (attenuated to approx. 20 A in 20 ms)
34 A
(attenuated to approx. 2 A in 20 ms)
MR-J4-700B(-RJ)
85 A (attenuated to approx. 20 A in 30 ms)
MR-J4-11KB(-RJ)
226 A (attenuated to approx. 30 A in 30 ms)
42 A
(attenuated to approx. 2 A in 30 ms)
MR-J4-15KB(-RJ)
226 A (attenuated to approx. 50 A in 30 ms)
MR-J4-22KB(-RJ)
226 A (attenuated to approx. 70 A in 30 ms)
(2) 400 V class
The following shows the inrush currents (reference data) that will flow when 480 V AC is applied at the
power supply capacity of 2500 kVA and the wiring length of 1 m.
Servo amplifier
Inrush currents (A
0-P
)
Main circuit power supply (L1/L2/L3)
Control circuit power supply (L11/L21)
MR-J4-60B4(-RJ)
MR-J4-100B4(-RJ)
65 A
(attenuated to approx. 5 A in 10 ms)
40 A to 50 A
(attenuated to approx. 0 A in 2 ms)
MR-J4-200B4(-RJ)
80 A
(attenuated to approx. 5 A in 10 ms)
MR-J4-350B4(-RJ)
100 A
(attenuated to approx. 20 A in 10 ms)
MR-J4-500B4(-RJ)
65 A
(attenuated to approx. 9 A in 20 ms)
41 A
(attenuated to approx. 0 A in 3 ms)
MR-J4-700B4(-RJ)
68 A
(attenuated to approx. 34 A in 20 ms)
MR-J4-11KB4(-RJ)
339 A
(attenuated to approx. 10 A in 30 ms)
38 A
(attenuated to approx. 1 A in 30 ms)
MR-J4-15KB4(-RJ)
339 A
(attenuated to approx. 15 A in 30 ms)
MR-J4-22KB4(-RJ)
339 A
(attenuated to approx. 20 A in 30 ms)
Содержание MR-J4-100B(-RJ)
Страница 17: ...8 MEMO ...
Страница 143: ...4 STARTUP 4 20 MEMO ...
Страница 199: ...5 PARAMETERS 5 56 MEMO ...
Страница 227: ...6 NORMAL GAIN ADJUSTMENT 6 28 MEMO ...
Страница 281: ...8 TROUBLESHOOTING 8 16 MEMO ...
Страница 303: ...9 DIMENSIONS 9 22 MEMO ...
Страница 319: ...10 CHARACTERISTICS 10 16 MEMO ...
Страница 429: ...11 OPTIONS AND PERIPHERAL EQUIPMENT 11 110 MEMO ...
Страница 435: ...12 ABSOLUTE POSITION DETECTION SYSTEM 12 6 MEMO ...
Страница 483: ...14 USING A LINEAR SERVO MOTOR 14 34 MEMO ...
Страница 531: ...16 FULLY CLOSED LOOP SYSTEM 16 26 MEMO ...
Страница 613: ...17 APPLICATION OF FUNCTIONS 17 82 MEMO ...
Страница 653: ...APPENDIX App 40 This certificate is valid until 2017 02 28 After March 2017 use certificate shown on the previous page ...
Страница 654: ...APPENDIX App 41 ...