11. OPTIONS AND PERIPHERAL EQUIPMENT
11 - 69
11.9 Selection example of wires
POINT
Refer to section 11.1.3 for SSCNET III cable.
To comply with the IEC/EN/UL/CSA standard, use the wires shown in app. 4 for
wiring. To comply with other standards, use a wire that is complied with each
standard.
For the selection example when the MR-J4-_B-RJ servo amplifier is used with
the DC power supply input, refer to app. 15.3.
Selection conditions of wire size are as follows.
Construction condition: Single wire set in midair
Wire length: 30 m or less
The following diagram shows the wires used for wiring. Use the wires given in this section or equivalent.
5) Power regeneration converter lead
Power regeneration
converter
N-
3) Regenerative option lead
Regenerative option
2) Control circuit power supply lead
C
P+
L1
L2
L3
L11
L21
1) Main circuit power supply lead
Power supply
Servo amplifier
U
V
W
M
4) Servo motor power supply lead
Содержание MR-J4-100B(-RJ)
Страница 17: ...8 MEMO ...
Страница 143: ...4 STARTUP 4 20 MEMO ...
Страница 199: ...5 PARAMETERS 5 56 MEMO ...
Страница 227: ...6 NORMAL GAIN ADJUSTMENT 6 28 MEMO ...
Страница 281: ...8 TROUBLESHOOTING 8 16 MEMO ...
Страница 303: ...9 DIMENSIONS 9 22 MEMO ...
Страница 319: ...10 CHARACTERISTICS 10 16 MEMO ...
Страница 429: ...11 OPTIONS AND PERIPHERAL EQUIPMENT 11 110 MEMO ...
Страница 435: ...12 ABSOLUTE POSITION DETECTION SYSTEM 12 6 MEMO ...
Страница 483: ...14 USING A LINEAR SERVO MOTOR 14 34 MEMO ...
Страница 531: ...16 FULLY CLOSED LOOP SYSTEM 16 26 MEMO ...
Страница 613: ...17 APPLICATION OF FUNCTIONS 17 82 MEMO ...
Страница 653: ...APPENDIX App 40 This certificate is valid until 2017 02 28 After March 2017 use certificate shown on the previous page ...
Страница 654: ...APPENDIX App 41 ...