9057
Event Log Database Item Size
RdOnly
Management information: The size of every item.
9058-9059
Event Log Database Size
RdOnly
Management information: The size of the database, the size
includes management information.
(Total_Item*Itmanagement_info_size).
9060-9075
Numeric Input Object and ASCII
Input Object data
RdOnly
These 16 registers represent the latest entries, when the OIT
operator enters a numeric or ASCII value into one of these
objects. Register 9075 is the latest entry.
9076-9079
Reserved for future use
9080-9085
Project name
RdOnly
Twelve bytes are used to store the project name. Use the ASCII
Data Object to display on OIT.
9086-9087
Project size
RdOnly
Four bytes are used to store the size of the current project (in
bytes). Use the Numeric Data Object (Decimal Display) to
display on OIT
9088-9089
Project size (Kbytes)
RdOnly
Four bytes are used to store the size of the current project (in
bytes). Use the Numeric Data Object (Decimal Display) to
display on OIT.
9090-9091
Compiler Version ID
RdOnly
Four bytes are used to store the compiler version of the current
project. Use the Numeric Data Object (Decimal Display) to
display on OIT.
9092
Project Compiled Date: Year
RdOnly
This register contains the year date when the project was last
compiled. Use the Numeric Data Object (Decimal Display) to
display on OIT.
9093
Project Compiled Date: Month
RdOnly
This register contains the month date when the project was last
compiled. Use the Numeric Data Object (Decimal Display) to
display on OIT.
9094
Project Compiled Date: Day
RdOnly
This register contains the day of month date when the project was
last compiled. Use the Numeric Data Object (Decimal Display) to
display on OIT.
9095-9099
Reserved for future use
9100
Indirect Window Object; window #
RdOnly
This register stores the window number requested using the
Indirect Window Object
9101
Indirect Window Object; Offset
R/W
This register can be used to store an offset that is added to
LW9100 when using the Indirect Window Object
9102-9129
Reserved for future use.
9130
Change language
R/W
V 2.5.0 -- This register changes the language set (Values:0-3)
9135
Battery Voltage (BIN)
RdOnly
V 2.6.0 - Li-Battery Measurement (If value = 1175 = 3.02V) (If
value <1070 or 2.75V, then replace the battery)
Create a Numeric Display for LW:9135, set "Input high=1175"
and set "engineering high = 302" Then display should show
proper voltage.
9136
CF Recipe Transfer
RdOnly
0:inactive
1:Transfer in process
2:Transfer complete
3:Transfer failed
9137-9999
Reserved for future use
Re served Rec ipe Word (RW) Ta ble
Address
Function
Access
Description
60000
Real Time Clock (RTC);
Seconds
R/W
This register is used to store the seconds count for the optional
RTC; BCD code, valid values 0-59
60001
Real Time Clock (RTC);
Minutes
R/W
This register is used to store the minutes count for the optional
RTC; BCD code, valid values 0-59
60002
Real Time Clock (RTC);
Hour
R/W
This register is used to store the hour count for the optional RTC;
BCD code, valid values 0-23
60003
Real Time Clock (RTC);
Day Of Month
R/W
This register is used to store the day of the month for the optional
RTC; BCD code, valid values 0-31
1010-1001a, Rev 02
168
Sil ver Se ries In stal la tion & Op er a tion Man ual
Содержание Silver HMI504T
Страница 1: ...1010 1001A Rev 02...
Страница 20: ...1010 1001a Rev 02 16 Silver Series Installation Operation Manual OIT to PC Serial Port Pin Assignments...
Страница 32: ...1010 1001a Rev 02 28 Silver Series Installation Operation Manual...
Страница 128: ...1010 1001a Rev 01 124 Silver Series Installation Operation Manual...
Страница 156: ...1010 1001a Rev 02 152 Silver Series Installation Operation Manual...
Страница 166: ...1010 1001a Rev 02 162 Silver Series Installation Operation Manual...
Страница 216: ...1010 1001a Rev 01 212 Silver Series Installation Operation Manual...
Страница 251: ...1010 1001a Rev 02 Macros 247 Set Bit Objects Attributes Dialog Project Example of Add 2...
Страница 264: ...End Macro_Command 1010 1001a Rev 02 260 Silver Series Installation Operation Manual...
Страница 268: ...1010 1001a Rev 01 264 Silver Series Installation Operation Manual...