9100-9227
PLC Communication Status
R/W
V 2.6.0 -- These bits are mapped to PLC Nodes 0-127. Bit
changes to 1 when the communication times out. Write 0 to
resume the communication.
9228-9355
AUX device Communication
Status
R/W
V 2.6.0 -- These bits are mapped to AUX device nodes 0-127. Bit
changes to 1 when the communication times out. Write to 0 to
resume communication.
9356-9959
Reserved for future use
9360
Compact Flash Status
RdOnly
0:CF not detected
1:CF detected
9361
Recipe Transfer from Compact
Flash
R/W
Set to 1 to start transfer.
9362-9999
Reserved for future use
Re served Lo cal Word (LW) Ta ble
Address
Function
Access
Description
9000
Recipe Index Base
R/W
RWI and RBI use this index to access recipe data. Maximum
value for correct functionality is 32,767.
9001
Reserved for future use
9002,9003
Maximum Value – Numeric Input
Object
RdOnly
This represents the maximum value allowed when a Numeric
Input Object is active. If no Numeric Input Object is active, the
value is 0.
9004,9005
Minimum Value – Numeric Input
Object
RdOnly
This represents the minimum value allowed when a Numeric
Input Object is active. If no Numeric Input Object is active, the
value is 0.
9006
Message Board Operation Mode
RdOnly
This value represents the current operation mode of the Message
Board. 0=open, 1=brush, 2=clipping
9007
Message Board Pen Width
RdOnly
This value represents the current pent width in pixels of the
Message Board
9008
Message Board Pen Color
RdOnly
This value represents the current pen color (0-255) of the
Message Board
9009
Reserved for future use
9010
Local second, (bcd, 0-59)
R/W
When the local Word Option is selected for RTC source in the
Edit System Parameters-General settings dialog box of
EasyBuilder, this is the location of the seconds parameter. Use
the Data Transfer Object to copy the PLC RTC seconds value to
this register.
9011
Local minute, (bcd, 0-59)
R/W
When the local Word Option is selected for RTC source in the
Edit System Parameters-General settings dialog box of
EasyBuilder, this is the location of the minutes parameter. Use
the Data Transfer Object to copy the PLC RTC minutes value to
this register.
9012
Local hour, (bcd, 0-23)
R/W
When the local Word Option is selected for RTC source in the
Edit System Parameters-General settings dialog box of
EasyBuilder, this is the location of the hours parameter. Use the
Data Transfer Object to copy the PLC RTC hours value to this
register.
9013
Local date, (bcd, 0-31)
R/W
When the local Word Option is selected for RTC source in the
Edit System Parameters-General settings dialog box of
EasyBuilder, this is the location of the date parameter. Use the
Data Transfer Object to copy the PLC RTC date value to this
register.
9014
Local month, (bcd, 0-11)
R/W
When the local Word Option is selected for RTC source in the
Edit System Parameters-General settings dialog box of
EasyBuilder, this is the location of the month parameter. Use the
Data Transfer Object to copy the PLC RTC month value to this
register.
1010-1001a, Rev 02
166
Sil ver Se ries In stal la tion & Op er a tion Man ual
Содержание Silver HMI504T
Страница 1: ...1010 1001A Rev 02...
Страница 20: ...1010 1001a Rev 02 16 Silver Series Installation Operation Manual OIT to PC Serial Port Pin Assignments...
Страница 32: ...1010 1001a Rev 02 28 Silver Series Installation Operation Manual...
Страница 128: ...1010 1001a Rev 01 124 Silver Series Installation Operation Manual...
Страница 156: ...1010 1001a Rev 02 152 Silver Series Installation Operation Manual...
Страница 166: ...1010 1001a Rev 02 162 Silver Series Installation Operation Manual...
Страница 216: ...1010 1001a Rev 01 212 Silver Series Installation Operation Manual...
Страница 251: ...1010 1001a Rev 02 Macros 247 Set Bit Objects Attributes Dialog Project Example of Add 2...
Страница 264: ...End Macro_Command 1010 1001a Rev 02 260 Silver Series Installation Operation Manual...
Страница 268: ...1010 1001a Rev 01 264 Silver Series Installation Operation Manual...