60004
Real Time Clock (RTC);
Month
R/W
This register is used to store the month for the optional RTC;
BCD code, valid values 0-11
60005
Real Time Clock (RTC);
Year
R/W
This register is used to store the year for the optional RTC; BCD
code, valid values 0-9999
60006
Real Time Clock (RTC);
Day of the Week
R/W
This register is used to store the day of the week for the optional
RTC; BCD code, valid values 0-6 (with 0=Sunday)
Non-vol a tile Stor age of Sys tem Pa ram e ters
System Parameters can be stored in the non-volatile memory held in the Recipe module. To enable this feature, see
the Hardware tab of the Set System Parameters dialog. Under the Edit menu, select System Parameters.
The OIT must be restarted in order to activate any changes.
The System Parameters are divided into three groups: PLC Settings, General Settings, Security Settings.
PLC Settings
Address
Function
Description
60040
Serial port
0:RS232, 1:RS485
60041
Baud Rate
0:9600, 1:192002:38400, 3:576004:115200
60042
Data Bits
0:7, 1:8
60043
Parity
0:none, 1:even, 2:odd
60044
Stop Bits
0:1, 1:2
60045
HMI Station Address
0-255
60046
PLC Station Address
0-255
60047
Multiple HMI
0:none, 1:master, 2:slave
60048
HMI-HMI link speed
0:38400, 1:115200
60049
PLC time out constant
60050
PLC block pack
General Settings
Address
Function
Access
Description
60051
Task button: Attribute
60052
Task button: Position
60053
Task button: background color
60054
Task button: Text
60055
Alarm bar: Pixel per scroll
60056
Alarm bar: Scroll speed
60057
Number of windows
60058
Reserved
60060
Startup window No.
60061
Backlight saver
R/W
This register is used to change the timer on the backlight saver
mode. (0=disable - Backlight is on all the time; 1-255=minutes
before the backlight goes off.)
60062
Cursor color
60064
Buzzer Enable
R/W
This register can change the state of the internal buzzer.
(0=disable buzzer from sounding; 1=enable buzzer to sound
when screen is touched).
60065
Common window: popup window
1010-1001a, Rev 02
Rep re senting Data with Graph ics Ob jects
169
Содержание Silver HMI504T
Страница 1: ...1010 1001A Rev 02...
Страница 20: ...1010 1001a Rev 02 16 Silver Series Installation Operation Manual OIT to PC Serial Port Pin Assignments...
Страница 32: ...1010 1001a Rev 02 28 Silver Series Installation Operation Manual...
Страница 128: ...1010 1001a Rev 01 124 Silver Series Installation Operation Manual...
Страница 156: ...1010 1001a Rev 02 152 Silver Series Installation Operation Manual...
Страница 166: ...1010 1001a Rev 02 162 Silver Series Installation Operation Manual...
Страница 216: ...1010 1001a Rev 01 212 Silver Series Installation Operation Manual...
Страница 251: ...1010 1001a Rev 02 Macros 247 Set Bit Objects Attributes Dialog Project Example of Add 2...
Страница 264: ...End Macro_Command 1010 1001a Rev 02 260 Silver Series Installation Operation Manual...
Страница 268: ...1010 1001a Rev 01 264 Silver Series Installation Operation Manual...