STEPS:
1. Connect the “OIT” end of the communication cable into either the RS-232 port or the RS-485 port as
required for your application (OIT housing is marked).
2. Tighten the two cable screws at each end to ensure shield ground path.
3. Route the communication cable to the PLC. Refer to the “OIT Cable Routing” section for more
information.
4. Connect the “PLC” end of the cable to the PLC and tighten the cable screws.
5. Connect the green shield wire from the cable to earth ground ( ) on the PLC. If this wire is not
present, make the ground connection inside the PLC connector.
6. The HMI530T/550T has a printer port and can be connected to an Epson compatible printer.
Panel Prep a ra tion
A metal panel or mounting surface with a minimum thickness of 15 gauge (0.059 inch/3.3mm) if cold-rolled steel or
hardened steel, or 10 gauge (0.101 inch/2.6mm) if aluminum alloy (6061-T6 preferred) is required. Thinner panels
or surfaces may bow between the mounting clamps and not form a seal with the gasket.
The area of the panel or mounting surface where the gasket comes into contact must be flat and free of scratches,
pits, and other features that prevent the gasket from sealing properly. If the panel or mounting surface is not
uniform, thick, flat, stiff, or smooth enough, then a sealant such as silicone may be required.
WARNING:
The OIT requires a stiff, flat, smooth mounting surface free of blemishes
to seal properly to NEMA 4.
1010-1001a, Rev 02
In stal la tion of OITs
13
Shielded Power Cable,
Maple P/N 6030-0009
HMI530
24V
GND
PLC [RS-485]
PRINTER
PC [RS-232]
PLC [RS-232]
OIT
Power Supply
Output
FG
DC Output -V (Gnd)
DC V (+24V)
Enhanced
models only
Enhanced
models only
Attach earth ground wire
(if included on cable)
Printer port
Power connector
Port 1, PLC[RS-232],
has a shielded female
DE9S connector
Port 2, PLC[RS-485]/
PC[RS-232],
has a shielded male
DE9P connector
Communication cable specific for
the PLC/Host; twisted pair, foil
shielded, 28AWG minimum
PLC/
Host
Printer
(Epson
Compatible)
Tighten all screws
Standard
printer cable
Port 1
Port 2
Earth
GND
Control
Panel
Ex am ple of Wir ing a Sil ver Series OIT to a PLC
Содержание Silver HMI504T
Страница 1: ...1010 1001A Rev 02...
Страница 20: ...1010 1001a Rev 02 16 Silver Series Installation Operation Manual OIT to PC Serial Port Pin Assignments...
Страница 32: ...1010 1001a Rev 02 28 Silver Series Installation Operation Manual...
Страница 128: ...1010 1001a Rev 01 124 Silver Series Installation Operation Manual...
Страница 156: ...1010 1001a Rev 02 152 Silver Series Installation Operation Manual...
Страница 166: ...1010 1001a Rev 02 162 Silver Series Installation Operation Manual...
Страница 216: ...1010 1001a Rev 01 212 Silver Series Installation Operation Manual...
Страница 251: ...1010 1001a Rev 02 Macros 247 Set Bit Objects Attributes Dialog Project Example of Add 2...
Страница 264: ...End Macro_Command 1010 1001a Rev 02 260 Silver Series Installation Operation Manual...
Страница 268: ...1010 1001a Rev 01 264 Silver Series Installation Operation Manual...