145
10 Configuration
10.11.3
Disturbance feedforward control
Open:
Device menu
r
Configuration
r
Controller
r
Controller 1 to 4
r
Disturbance feedforward control
Configuration point Selection/
setting option
Explanation
additive var. disturb.
Selection from
Analog selector
Analog input for the additive variable disturbance
The additive output level component
Y
add
added. This is calculated
as follows:
Y
add
= X × [(Y
2
- Y
1
) ÷ (X
2
- X
1
)] + Y
1
Y
add
: Additive output level component
X: Variable disturbance value
X
1
: Additive var. disturb. X start value
X
2
: Additive var. disturb. X end value
Y
1
: Additive var. disturb. Y start value
Y
2
: Additive var. disturb. Y end value
Additive var. disturb.
X
Start value
-99999 to +99999
Smallest value of the variable disturbance
Additive var. disturb.
X
Final value
-99999 to +99999
Largest value of the variable disturbance
Additive var. disturb.
Y
Start value
-100 to +100%
Additive output level component with largest
variable disturbance value
Additive var. disturb.
Y
Final value
-100 to +100%
Additive output level component with largest
variable disturbance value
X
Y
add
Y
1
X
1
Y
2
X
2
Содержание AQUIS touch P 202580
Страница 12: ...Content...
Страница 26: ...4 Identifying the device version 26...
Страница 29: ...29 5 Mounting Mounting depth with Ci conductivity sensor 283 3 mm 2 3 mm 36 mm 25 mm 23 2 mm...
Страница 32: ...5 Mounting 32...
Страница 64: ...7 Startup 64...
Страница 100: ...1 2 3 4 5...
Страница 107: ...107 8 Operation Example of a Quad View...
Страница 108: ...8 Operation 108...
Страница 114: ...9 Parameterization 114...
Страница 160: ...10 Configuration 160...
Страница 182: ...13 Calibrating a pH measuring chain 182...
Страница 196: ...16 Calibrating CR conductivity sensors 196...
Страница 206: ...17 Calibrating Ci conductivity sensors 206...
Страница 214: ...18 Calibrating universal inputs 214...
Страница 228: ...19 PC Setup Program 228...
Страница 319: ...319 20 Technical data...
Страница 320: ...20 Technical data 320...
Страница 321: ......