10 Configuration
140
10.11 Controller
10.11.1
Configuration of the controllers
Open:
Device menu
r
Configuration
r
Controller
r
Controller 1 to 4
r
Configuration
Configuration point Selection/
setting option
Explanation
Controller type
Two-point controller
Three-state controller,
Coarse-/fine controller,
Modulating controller,
continuous controller
with integrated
position controller,
Continuous controller
Selection of controller type
Control direction
Inverse
Direct
Inverse:
Output increases with negative control
deviation (actual value < setpoint value),
output decreases with positive control deviation
direct:
Output level increase with positive control
the deviation (actual value >setpoint value),
Output value decrease with negative control de-
viation
Output type 1
Pulse length output
Pulse frequency output
Continuous output
Signal type of controller output signal
Output type 2
Output contact type
1 to 2
Normally-closed contact
Working contact
Contact type (control direction) of the digital con-
troller outputs (K1,K2)
Working contact corresponds to a normally-open
contact
Resting contact corresponds to a normally-
closed contact
Manual mode
Enabled
Disabled
Enabling of manual mode
Acceptance of
manual output 1
Yes
No
Acceptance of the preconfigured manual output
(for the 1st controller output on coarse-/fine con-
trollers) upon activation of the manual mode
Man. output level 1
-100 to +100%
Preconfigured Man. output level (for the 1st con-
troller output on coarse/fine controllers)
Accepted automatically on activation of the
"manual mode" if acceptance of the manual out-
put level is set to "Yes".
Otherwise, the controller accepts the last output
level from the automatic control mode.
Acceptance of manual
output 2
Yes
No
only for coarse/fine controllers:
Acceptance of the preconfigured manual output
for the 2nd controller output upon activation
of the manual mode
Содержание AQUIS touch P 202580
Страница 12: ...Content...
Страница 26: ...4 Identifying the device version 26...
Страница 29: ...29 5 Mounting Mounting depth with Ci conductivity sensor 283 3 mm 2 3 mm 36 mm 25 mm 23 2 mm...
Страница 32: ...5 Mounting 32...
Страница 64: ...7 Startup 64...
Страница 100: ...1 2 3 4 5...
Страница 107: ...107 8 Operation Example of a Quad View...
Страница 108: ...8 Operation 108...
Страница 114: ...9 Parameterization 114...
Страница 160: ...10 Configuration 160...
Страница 182: ...13 Calibrating a pH measuring chain 182...
Страница 196: ...16 Calibrating CR conductivity sensors 196...
Страница 206: ...17 Calibrating Ci conductivity sensors 206...
Страница 214: ...18 Calibrating universal inputs 214...
Страница 228: ...19 PC Setup Program 228...
Страница 319: ...319 20 Technical data...
Страница 320: ...20 Technical data 320...
Страница 321: ......