Item
Description
priority of 15 will be shown as critical priority alarms on the Alarm Summary and
other displays. For information about how to enable critical alarms, see
“Customizing alarm colors” in the
Station Configuration Guide
.
Subpriority
The optional sub-priority level of the alarm, between 0 (lowest and default) and 15
(highest).
Deadband
You can specify a percentage value that is used in determining what constitutes a
good control. This is called control deadband. A control deadband works as fol-
lows. If the PV signal, read back after an SP control is issued, does not reach the
following value within the period specified for the Control Timeout option, a PV
Fail alarm is generated: New SP Value \± Deadband Percentage This check is per-
formed every 10 seconds (from when the control is performed) until good control
has been achieved or the control timeout period has elapsed (whichever happens
first).
Unreasonable
Value Alarm
The On Delay, Off Delay, Priority, and Subpriority values for the unreasonable
value alarm.
The high and low limits for unreasonable values are defined on
Point Processing
tab on the
Message & Point Processing
display. The values are entered as a
percentage of the point range.
Control Failure Alarms
PV Control
Fail Alarm
The Priority and Subpriority values for the PV control fail alarm.
Control
Timeout
The maximum time (in seconds) allowed, after a change in SP or OP, for the PV
value to reach an acceptable value before a control fail alarm is raised. The
default is None (no control timeout).
The server checks the value every 10 seconds during the timeout period.
You must specify a value other than Nil to enable the control fail alarm.
Control Dead-
band
The percentage deviation from the SP value that constitutes a good control. (The
default value is 1.000%.) The value is calculated using the formula:
(new SP value) +/- (control deadband percentage) If the PV value is not within the
target range, a PV fail alarm is raised.
External Change Alarms
PV
When selected, an alarm is raised if the PV parameter changes without the
change being initiated from the server.
Set point
When selected, an alarm is raised if the PV parameter changes without the
change being initiated from the server.
Displaying detailed process information
Honeywell 2017
209