Function
Experion server unavailable
Log on to Console Station
Yes
Change your password using
Console Station
Yes, if you are using a Windows-based user account that is
configured in Experion.
No, if you are using a traditional operator account.
View and control points
Yes, for points from direct data sources, such as Process
Controllers.
No, for points from scan-based controllers.
View custom displays
Yes, however only data from direct data sources is
available.
View and acknowledge alarms on
the Alarm Summary
Yes, for alarms from direct data sources.
Add comments to an alarm
No
Print the Alarm Summary as a
report
No
View the status of items in the
System Components tree in the
System Status display
Yes, for equipment that is directly connected to the Console
Station, such as Process Controllers. The status of other
items is shown as unknown.
View and acknowledge system
alarms on the System Status
display
Yes, for equipment that is directly connected to the Console
Station, such as Process Controllers. Other alarms are
shown as questionable.
View faceplates in the Status pane
on the System Status display
Yes, for equipment that is directly connected to the Console
Station, such as Process Controllers.
View and respond to events
No
Add comments to an event
No
Create operator recorded events
No
Print the Event Summary as a
report
No
Event archiving
No
View and respond to messages
Yes, for messages from direct data sources.
Load recipes
No
Reports
No
View trends
Yes, but limited to real-time trending of points from direct
data sources. (Historical data is not available.)