![Honeywell Experion LX Скачать руководство пользователя страница 164](http://html.mh-extra.com/html/honeywell/experion-lx/experion-lx_operators-manual_149110164.webp)
Tip:
To add columns other than these to the current display, click the Show column
organizer icon to display the full list of available columns, and then select those
you would like included.
Column
Description
Date &
Time
The time and date at which the event was received.
Location
The tag name of the asset to which the point or device belongs.
Source
The point or device that caused the event.
If the point ID is too long to be fully displayed in the alarm summary, it is truncated.
To see the full name place the mouse pointer over the partial point ID to display the
full point ID.
Condition
The event condition.
Action
The action, either operator or system generated.
ACK. Alarm acknowledged.
ACK PNT. All alarms on a point acknowledged at the same time. That is, the user
has selected an object on a schematic and pressed the
Ack
key. Each alarm that
was acknowledged is journaled, as is the summary
ACK.PNT
event. For example,
for a point with PVHI and PVHIHI alarms active, three events are journaled: ACK
for PVHI, ACK for PVHIHI, and the ACK PNT summary.
DISCARD. Alarm discarded due to alarm list overflow.
OK. Alarm returned to normal.
SHELVE. Alarm shelved.
UNSHELVE. Alarm unshelved.
ACTIVE. Suppression group activated.
INACTIVE. Suppression group deactivated.
SUPP. Alarm has been suppressed.
UNSUPP. Alarm has been unsuppressed.
Blank. No action has occurred.
For a list of Safety Manager actions, refer to the “SOE log entries reference” topic
in the
Safety Manager Integration Guide
.
Responding to events
Honeywell 2017
164
Содержание Experion LX
Страница 1: ...Experion LX Operator s Guide EXDOC XX80 en 500A April 2017 Release 500 ...
Страница 77: ...Button Description toolbar Using faceplates Honeywell 2017 77 ...
Страница 249: ...n Restart n Hold n Stop n Abort n Resume n Active n Cancel About activities batches and procedures Honeywell 2017 249 ...