n
Minimum security level required to suppress audible annunciations. That is, OPER,
SUPV, ENGR, and MNGR.
Users with a security level less than the minimum level required are unable suppress
audible annunciations.
n
Audible suppression duration, in seconds. The default period is 600 seconds (10
minutes) and the maximum period is 3,600 seconds (1 hour).
n
Maximum suppressible priority. That is, Low or High.
Alarm priority
…includes these alarms and messages
Low
Low priority process alarms
Low priority system alarms
Info messages
Confirmable messages
High
Low priority alarms and messages
High priority process alarms
High priority system alarms
Maximum suppressible priorities
Note that all existing alarms (including urgent alarms) are silenced when the
Suppress
audible annunciations
button is clicked. However, audible annunciation of urgent
alarms that occur after the initial silencing is not suppressed. Urgent alarms include
urgent system alarms and urgent process alarms.
Suppression button behavior
The
Suppress audible annunciations
button that appears on the Alarm Summary comprises
three icons: Urgent, High, and Low.
As you click the button, its behavior changes, based on the type of audible annunciation
configured for your system. The button can have up to three states:
When the button looks like this…
…you will hear audible annunciation of
All alarms and messages.
High priority alarms and urgent priority alarms.
Suppression button states
Responding to alarms