Test Operation
SiEN34-705
90
General Information
4.4.1.3 Simplified Remote Control
BRC2A51
BRC2C51
1. Remove the upper part of remote control.
2. When in the normal mode, press the [BS6] BUTTON (
2
) (field set), and the FIELD SET
MODE is entered.
3. Select the desired MODE No. with the [BS2] BUTTON (
3
) (temperature setting
s
) and the
[BS3] BUTTON (
3
) (temperature setting
t
).
4. During group control, when setting by each indoor unit (mode No. 20, 22, and 23 have been
selected), push the [BS8] (
4
) BUTTON (unit No.) and select the INDOOR UNIT NO. to be
set. (This operation is unnecessary when setting by group.)
5. Push the [BS9] BUTTON (
5
) (set A) and select FIRST CODE NO.
6. Push the [BS10] BUTTON (
6
) (set B) and select SECOND CODE NO.
7. Push the [BS7] BUTTON (
7
) (set/cancel) once and the present settings are SET.
8. Push the [BS6] BUTTON (
8
) (field set) to return to the NORMAL MODE.
9. (Example) If during group setting and the time to clean air filter is set to FILTER
CONTAMINATION - HEAVY, SET MODE NO. to “10”, FIRST CODE NO. to “0”, and
SECOND CODE NO. to “02”.
Mode No.
Second
code no.
First
code no.
Unit No.