SiEN34-705
Test Operation
General Information
109
The numbers in the "No." column represent the number of times to press the
SET (BS2) button.
Setting item 0 Display contents of “Number of units for various settings”
No.
Setting item
LED display
Data display
H1P H2P H3P H4P H5P H6P H7P
0
Various settings
9 7 7 7 7 7 7
Lower 4 digits
1
C/H unified address
9 7 7 7 7 7 8
Lower 6 digits
2
Low noise/demand address
9 7 7 7 7 8 7
3
Not used
9 7 7 7 7 8 8
4
Airnet address
9 7 7 7 8 7 7
5
Number of connected indoor units
9 7 7 7 8 7 8
6
Number of connected BS units
9 7 7 7 8 8 7
7
Number of connected zone units
(excluding outdoor and BS unit)
9 7 7 7 8 8 8
8
Number of outdoor units
9 7 7 8 7 7 7
9
Number of connected BS units
9 7 7 8 7 7 8
Lower 4 digits:
upper
10
Number of connected BS units
9 7 7 8 7 8 7
Lower 4 digits:
lower
11
Number of zone units (excluding
outdoor and BS unit)
9 7 7 8 7 8 8
Lower 6 digits
12
Number of terminal blocks
9 7 7 8 8 7 7
Lower 4 digits:
upper
13
Number of terminal blocks
9 7 7 8 8 7 8
Lower 4 digits:
lower
14
Contents of malfunction (the
latest)
9 7 7 8 8 8 7
Malfunction
code table
15
Contents of malfunction
(1 cycle before)
9 7 7 8 8 8 8
16
Contents of malfunction
(2 cycle before)
9 7 8 7 7 7 7
20
Contents of retry (the latest)
9 7 8 7 8 7 7
21
Contents of retry (1 cycle before)
9 7 8 7 8 7 8
22
Contents of retry (2 cycle before)
9 7 8 7 8 8 7
25
Number of multi connection
outdoor units
9 7 8 8 7 7 8
Lower 6 digits
EMG operation /
backup operation
setting
ON
9 7 7 8 7 7 7
OFF
9 7 7 7 7 7 7
Defrost select setting
Short
9 7 7 7 8 7 7
Medium
9 7 7 7 9 7 7
Long
9 7 7 7 7 7 7
Te setting
H
9 7 7 7 7 8 7
M
9 7 7 7 7 9 7
L
9 7 7 7 7 7 7
Tc setting
H
9 7 7 7 7 7 8
M
9 7 7 7 7 7 9
L
9 7 7 7 7 7 7
<Selection of setting item>
<Confirmation on setting contents>
To enter the monitor mode, push the
MODE (BS1) button when in “Setting
mode 1”.
Push the SET (BS2) button and set
the LED display to a setting item.
Push the RETURN (BS3) button to
display different data of set items.
Push the RETURN (BS3) button and
switches to the initial status of
“Monitor mode”.
∗
Push the MODE (BS1) button and
returns
to
“Setting
mode
1”.
c. Monitor mode
(V2765)