Heat Pump / Cooling Only 50Hz (RX(Y)Q5~54P)
SiEN34-705
218
Installation Manual
3.2 Introduction
!
RX(Y)Q-P series are designed for outdoor installation and used for cooling and heatpump
(except RXQ-P) applications. Outdoor units come in three standard sizes, and with a single
system through a multi system combining up to three outdoor units, rated cooling capacity
from 14.0 kW to 147 kW and rated heating capacity from 16.0 kW to 170 kW (except RXQ-P)
can be achieved.
!
The RX(Y)Q-P units can be combined with Daikin VRV series indoor units for air
conditioning purposes. Always use appropriate indoor units compatible with R-410A. To lean
which models of indoor units are compatible with R-410A, refer to the product catalogs.
To combine with other refrigerant indoor unit will cause malfunction.
3.2.1 Combination
The indoor units can be installed in the following range.
(The total number of indoor units cannot exceed 64 units.)
<Outdoor unit>
<Total capacity of indoor units>
<Total quantity of indoor units>
RX(Y)Q5PY1...................... 62.5 ~ 250
12 units
RX(Y)Q8PY1.................... 100
~ 400
20 units
RX(Y)Q10PY1................. 125
~ 500
25 units
RX(Y)Q12PY1.................. 150
~ 600
30 units
RX(Y)Q14PY1.................. 175
~ 700
35 units
RX(Y)Q16PY1.................. 200
~ 800
40 units
RX(Y)Q18PY1.................. 225
~ 900
45 units
RX(Y)Q20PY1.................. 250
~ 800
40 units
RX(Y)Q22PY1.................. 275
~ 880
44 units
RX(Y)Q24PY1.................. 300
~ 960
48 units
RX(Y)Q26PY1.................. 325
~ 1040
52 units
RX(Y)Q28PY1.................. 350
~ 1120
56 units
RX(Y)Q30PY1.................. 375
~ 1200
60 units
RX(Y)Q32PY1.................. 400
~ 1280
64 units
RX(Y)Q34PY1.................. 425
~ 1360
64 units
RX(Y)Q36PY1.................. 450
~ 1440
64 units
RX(Y)Q38PY1.................. 475
~ 1235
61 units
RX(Y)Q40PY1.................. 500
~ 1300
64 units
RX(Y)Q42PY1.................. 525
~ 1365
64 units
RX(Y)Q44PY1.................. 550
~ 1430
64 units
RX(Y)Q46PY1.................. 575
~ 1495
64 units
RX(Y)Q48PY1.................. 600
~ 1560
64 units
RX(Y)Q50PY1.................. 625
~ 1625
64 units
RX(Y)Q52PY1.................. 650
~ 1690
64 units
RX(Y)Q54PY1.................. 675
~ 1755
64 units
Note:
!
Be sure to connect an R-410A indoor unit.
See the catalog for indoor unit models which can be connected.
!
At above is the total capacity and total number of units of the indoor units when configured in
a standard combination. See the technical reference for details on total capacity and total
number of indoor units when using a configuration other than the standard combination. The