Heat Pump 60Hz (RXYQ5~54P)
SiEN34-705
292
Installation Manual
!
The L1, L2, L3 and N phases of the power wiring should be secured separately to the hook
using the included clamp (1).
!
The ground wiring should be bound to the power wiring using the included clamp (1) to
prevent outside force from being applied to the terminal area.
!
Wire so that the ground wiring does not come into contact with the compressor lead wiring. If
they touch, this may have an adverse effect on other devices.
Caution:
!
Be sure to use crimp-style terminal with insulating sleeves for connections. (See the figure
below.)
!
For wiring, use the designated power wire and connect firmly, then secure to prevent outside
pressure being exerted on the terminal board.
!
Use an appropriate screwdriver for tightening the terminal screws. A screwdriver with a small
head will strip the head and make proper tightening impossible.
!
Over-tightening the terminal screws may break them.
See the following table for the tightening torque of the terminal screws.
!
When pulling the ground wire out, wire it so that it comes through the cut out section of the
cup washer. (See the figure below.) An improper ground connection may prevent a good
ground from being achieved.
!
When two wires are connected to a single terminal, connect them so that the rear sides of
the crimp contacts face each other. Also, make sure the thinner wire is on top, securing the
two wires simultaneously to the resin hook using the included clamp (1).
L1
L2
L3
N
Ground wire
Ground terminal
Ground wire
Clamp (1) (accessory)
Clamp (1) (accessory)
Power supply
(3N~50Hz 380-415V)
Branch switch,
Overcurrent breaker
Earth leakage
circuit breaker
Attach insulation
sleeves
Power supply
terminal block
figure 26
Screw size
Tightening torque (N·m)
M8 Power terminal, ground terminal
5.5 ~7.3
Power wire
Crimp-
s
tyle termin
a
l
In
su
l
a
ting
s
leeve
Crimp-style terminal
Cup washer
Cut out section
Wire: n
a
rrow
Wire: thick
Re
s
in hook
Termin
a
l
b
lock