Heat Pump / Cooling Only 50Hz (RX(Y)Q5~54P)
SiEN34-705
222
Installation Manual
3.3 Selection of Location
Select a location for installation that meets the following conditions. Get the customer’s
permission.
1. There is no danger of fire due to leakage of inflammable gas.
2. Select the location of the unit in such a way that neither the discharged air nor the sound
generated by the unit disturb anyone.
3. The foundation is strong enough to support the weight of the unit and the floor is flat to
prevent vibration and noise generation.
4. The piping length between the outdoor unit and the indoor unit may not exceed the allowable
piping length. (Refer to
“1-6 Refrigerant Piping”
)
5. Locations where the unit’s suction vent and outlet vent do not generally face the wind.
Wind blowing directly into the suction or outlet vents will interfere with the unit’s operation.
If necessary, install some kind of obstruction to block the wind.
6. The space around the unit is adequate for servicing and the minimum space for air inlet and
air outlet is available.
(See the “Installation Space Examples” for the minimum space requirements.)
Installation Space Examples
!
The installation space requirement shown in figure 3 is a reference for cooling operation
when the outdoor temperature is 35°C.
If the design outdoor temperature exceeds 35°C or the heat load exceeds maximum
capacity in all the outdoor unit, take an even large space on the intake shown in figure 3.
!
During installation, install the units using the most appropriate of the patterns shown in figure
3 for the location in question, taking into consideration human traffic and wind.
!
If the number of units installed is more than that shown in the pattern in figure 3, install the
units so there are no short circuits.
!
As regards space in front of the unit, consider the space needed for the local refrigerant
piping when installing the units.
!
If the work conditions in figure 3 do not apply, contact your dealer or Daikin directly.
≥
10
≥
10
≥
10
≥
20
≥
20
≥
50
≥
50
≥
50
≥
200
≥
400
≥
400
≥
50
≥
10
≥
300
≥
300
≥
500
≥
500
≥
500
≥
500
≥
100
≥
100
≥
100
≥
100
≥
300
≥
200
≥
300
Service space of front side
Service space of front side
Service space of front side
Service space of front side
Service space of suction side
Service space of suction side
Service space of suction side
Service space of suction side
No limit to wall height
No limit to wall height
< If
installed as a single unit >
< When
installed in serial
(Pattern 1)
(Pattern 2)
(Pattern 3)
(Pattern 1)
(Pattern 2)
(Pattern 3)
figure 3
Front
side
Front
side
Front
side
Front
side
Front
side
Front
side