1.11 Additional Refrigerant Charge and Check Operation
The outdoor unit is charged with refrigerant when shipped from the factory, but depending on
the size and length of the piping when installed, it may require additional charging.
For charging the additional refrigerant, follow the procedure in this chapter.
And then carry out the check operation.
1.11.1 Before working
[About the refrigerant tank]
Check whether the tank has a siphon pipe before charging and place the tank so that the
refrigerant is charged in liquid form. (See the figure below.)
Caution:
!
Always use the proper refrigerant (R-410A). If charged with the refrigerant containing an
improper material, it may cause an explosion or accident.
!
R-410A is a mixed refrigerant, so charging it as a gas will cause the refrigerant composition
to change, which may prevent normal operation.
[Shutoff valve operation procedure]
When operating the shutoff valve, follow the procedure instructed below.
Note:
!
Do not open the shutoff valve until “1-10 Checking of Device and Installation Conditions” are
completed. If the shutoff valve is left open without turning on the power, it may cause
refrigerant to buildup in the compressor, leading insulation degradation.
!
Be sure to use the correct tools.
The shutoff valve is not a back-seat type. If forced it to open, it might break the valve body.
!
When using a service port, use the charge hose.
!
After tightening the cap, make sure no refrigerant gas is leaking.
[Tightening torque]
The sizes of the shutoff valves on each model and the tightening torque for each size are listed
in the table below.
<Size of Shutoff Valve>
With siphon pipe
Other tanks
S
t
a
nd the t
a
nk
u
pright
a
nd ch
a
rge.
(The
s
iphon pipe goe
s
a
ll the w
a
y in
s
ide,
s
o the t
a
nk doe
s
not need
b
e p
u
t
u
p
s
ide-down ch
a
rge in li
qu
id form.)
S
t
a
nd the t
a
nk
u
p
s
ide-down
a
nd ch
a
rge.
5HP type
8HP type
10HP type 12HP type 14HP type 16HP type 18HP type
Liquid side
shutoff
valve
φ
9.5
The 12HP type corresponds to the 12.7-diameter
onsite piping using the included piping.
φ
12.7
The 18HP type corresponds to the
15.9-diameter onsite piping using
the accessory pipe.
Gas side
shutoff
valve
φ
15.9
φ
19.1
φ
25.4
The 10HP type corresponds to the 22.2-diameter onsite piping
using the accessory pipe.
The 12 ~ 18HP type corresponds to the 28.6-diameter onsite
piping using the accessory pipe.