Heat Pump / Cooling Only 50Hz (RX(Y)Q5~54P)
SiEN34-705
238
Installation Manual
1.7 Field Wiring
Caution:
!
All field wiring and components must be installed by a licensed electrician and must comply
with relevant local and national regulations.
!
Be sure to use a dedicated power circuit. Never use a power supply shared by another
appliance.
!
Never install a phase advancing capacitor. As this unit is equipped with an inverter, installing
a phase advancing capacitor will not only deteriorate power factor improvement effect, but
also may cause capacitor abnormal heating accident due to high-frequency waves.
!
Only proceed with wiring work after blocking off all power.
!
Always ground wires in accordance with relevant local and national regulations.
!
This machine includes an inverter device. Connect earth and leave charge to eliminate the
impact on other devices by reducing noise generated from the inverter device and to prevent
leaked current from being charged in the outer hull of the product.
!
Do not connect the ground wire to gas pipes, sewage pipes, lightning rods, or telephone
ground wires.
Gas pipes:
can explode or catch fire if there is a gas leak.
Sewage pipes:
no grounding effect is possible if hard plastic piping is used.
Telephone ground wires and lightning rods:
dangerous when struck by lightning due to
abnormal rise in electrical potential in the grounding.
!
Be sure to install an earth leakage circuit breaker.
This unit uses an inverter, so install the earth leakage circuit breaker that be capable of
handling high harmonics in order to prevent malfunctioning of the earth leakage circuit
breaker itself.
!
Earth leakage circuit breaker which are especially for protecting ground-faults should be
used in conjunction with main switch or fuse for use with wiring.
Note:
!
Electrical wiring must be done in accordance with the wiring diagrams and the description
herein.
!
Do not operate until refrigerant piping work is completed.
(If operated before complete the piping work, the compressor may be broken down.)
!
Never remove thermistor, sensor or etc. when connecting power wiring and transmission
wiring.
(If operated with thermistor, sensor or etc. removed, the compressor may be broken down.)
!
This product have reversed phase protection detector that only works when the power is
turned on. If there exists black out or the power goes on and off which the product is
operating, attach a reversed phase protection circuit locally. Running the product in reversed
phase may break the compressor and other parts.
!
Attach the power wire securely. Introducing power with a missing N-phase or with a
mistaken N-phase will break the unit.
!
Never connect the power supply in reversed phase.
The unit can not operate normally in reversed phase.
If you connect in reversed phase, replace two of the three phases.
!
Make sure the electrical unbalance ratio is no greater than 2%. If it is larger than this, the
unit’s life span will be reduced.
If the ratio exceeds 4%, the unit will shut down and an malfunction code will be displayed on
the indoor remote control.
!
Connect the wire securely using designated wire and fix it with attached clamp without
applying external pressure on the terminal parts (terminal for power wiring, terminal for
transmission wiring and earth terminal).