SiEN34-705
Heat Pump / Cooling Only 50Hz (RX(Y)Q5~54P)
Installation Manual
239
1.7.1 Power circuit, safety device, and cable requirements
!
A power circuit (see the following table) must be provided for connection of the unit. This
circuit must be protected with the required safety devices, i.e. a main switch, a slow blow
fuse on each phase and an earth leakage circuit breaker.
!
When using residual current operated circuit breakers, be sure to use a high-speed type (1
second or less) 200mA rated residual operating current.
!
Use copper conductors only.
!
Use insulated wire for the power cord.
!
Select the power supply cable type and size in accordance with relevant local and national
regulations.
!
Specifications for local wiring are in compliance with IEC60245.
!
Use wire type H05VV when protected pipes are used.
Use wire type H07RN-F when protected pipes are not used.
Note:
The above table indicates power specifications for standard combinations (see 1-2
Introduction).
If using anything other than the above combinations in a multi system, calculate using the
following procedure.
Minimum circuit amp value: add the minimum circuit amp values for each independent unit
Recommended fuse capacity: select the fuse capacity with the next higher value of the
calculated minimum circuit amp. multiplied by 1.1.
Ex: Combining the RXYQ30PY1 using RXYQ8PY1, RXYQ10PY1, and RXYQ12PY1.
Minimum circuit amp. of the RXYQ8PY1 in table above = 18.5 A
Minimum circuit amp. of RXYQ10PY1 in table above = 21.6 A
Minimum circuit amp. of RXYQ12PY1 in table above = 22.7 A
Accordingly, the minimum circuit amp. of the RXYQ30PY1 = 18.5 + 21.6 + 22.7= 62.8 A
Multiplying the result above by 1.1 (62.8 × 1.1) = 69.1 A, so the recommended fuse capacity
would be 70 A.
Phase and
frequency
Voltage
Minimum circuit
amp.
Recommended
fuses
RX(Y)Q5PY1
φ
3, 50Hz
380-415V
11.9A
15A
RX(Y)Q8PY1
φ
3, 50Hz
380-415V
18.5A
25A
RX(Y)Q10PY1
φ
3, 50Hz
380-415V
21.6A
25A
RX(Y)Q12PY1
φ
3, 50Hz
380-415V
22.7A
25A
RX(Y)Q14PY1
φ
3, 50Hz
380-415V
31.5A
35A
RX(Y)Q16PY1
φ
3, 50Hz
380-415V
31.5A
35A
RX(Y)Q18PY1
φ
3, 50Hz
380-415V
32.5A
40A
RX(Y)Q20PY1
φ
3, 50Hz
380-415V
41.2A
50A
RX(Y)Q22PY1
φ
3, 50Hz
380-415V
44.3A
50A
RX(Y)Q24PY1
φ
3, 50Hz
380-415V
50.0A
60A
RX(Y)Q26PY1
φ
3, 50Hz
380-415V
51.0A
60A
RX(Y)Q28PY1
φ
3, 50Hz
380-415V
54.1A
60A
RX(Y)Q30PY1
φ
3, 50Hz
380-415V
55.2A
70A
RX(Y)Q32PY1
φ
3, 50Hz
380-415V
63.0A
70A
RX(Y)Q34PY1
φ
3, 50Hz
380-415V
64.0A
80A
RX(Y)Q36PY1
φ
3, 50Hz
380-415V
65.0A
80A
RX(Y)Q38PY1
φ
3, 50Hz
380-415V
73.7A
90A
RX(Y)Q40PY1
φ
3, 50Hz
380-415V
81.5A
90A
RX(Y)Q42PY1
φ
3, 50Hz
380-415V
82.5A
100A
RX(Y)Q44PY1
φ
3, 50Hz
380-415V
83.5A
100A
RX(Y)Q46PY1
φ
3, 50Hz
380-415V
86.6A
100A
RX(Y)Q48PY1
φ
3, 50Hz
380-415V
87.7A
100A
RX(Y)Q50PY1
φ
3, 50Hz
380-415V
96.5A
110A
RX(Y)Q52PY1
φ
3, 50Hz
380-415V
96.5A
110A
RX(Y)Q54PY1
φ
3, 50Hz
380-415V
97.5A
110A