SiEN34-705
Heat Pump 60Hz (RXYQ5~54P)
Installation Manual
265
2.2 Introduction
!
RXYQ-P series are designed for outdoor installation and used for cooling and heatpump
applications. Outdoor units come in three standard sizes, and with a single system through a
multi system combining up to three outdoor units, rated cooling capacity from 14.0 kW to 147
kW and rated heating capacity from 16.0 kW to 170 kW can be achieved.
!
The RXYQ-P units can be combined with Daikin VRV series indoor units for air conditioning
purposes. Always use appropriate indoor units compatible with R-410A. To lean which
models of indoor units are compatible with R-410A, refer to the product catalogs.
To combine with other refrigerant indoor unit will cause malfunction.
2.2.1 Combination
The indoor units can be installed in the following range.
<Outdoor unit>
<Total capacity of indoor units>
<Total quantity of indoor units>
RXYQ5PYL(E) ................... 62.5 ~ 250
12 units
RXYQ8PYL(E) ................. 100
~ 400
20 units
RXYQ10PYL(E) .............. 125
~ 500
25 units
RXYQ12PYL(E) ............... 150
~ 600
30 units
RXYQ14PYL(E) ............... 175
~ 700
35 units
RXYQ16PYL(E) ............... 200
~ 800
40 units
RXYQ18PYL(E) ............... 225
~ 900
45 units
RXYQ20PYL(E) ............... 250
~ 800
40 units
RXYQ22PYL(E) ............... 275
~ 880
44 units
RXYQ24PYL(E) ............... 300
~ 960
48 units
RXYQ26PYL(E) ............... 325
~ 1040
52 units
RXYQ28PYL(E) ............... 350
~ 1120
56 units
RXYQ30PYL(E) ............... 375
~ 1200
60 units
RXYQ32PYL(E) ............... 400
~ 1280
64 units
RXYQ34PYL(E) ............... 425
~ 1360
64 units
RXYQ36PYL(E) ............... 450
~ 1440
64 units
RXYQ38PYL(E) ............... 475
~ 1235
61 units
RXYQ40PYL(E) ............... 500
~ 1300
64 units
RXYQ42PYL(E) ............... 525
~ 1365
64 units
RXYQ44PYL(E) ............... 550
~ 1430
64 units
RXYQ46PYL(E) ............... 575
~ 1495
64 units
RXYQ48PYL(E) ............... 600
~ 1560
64 units
RXYQ50PYL(E) ............... 625
~ 1625
64 units
RXYQ52PYL(E) ............... 650
~ 1690
64 units
RXYQ54PYL(E) ............... 675
~ 1755
64 units
Note:
!
Be sure to connect an R-410A indoor unit.
See the catalog for indoor unit models which can be connected.
!
At above is the total capacity and total number of units of the indoor units when configured in
a standard combination. See the technical reference for details on total capacity and total
number of indoor units when using a configuration other than the standard combination. The
standard combination are as follows.