Test Operation
SiEN34-705
100
General Information
How to Select
Operation Mode
Whether operation by remote control will be possible or not for turning on/off, controlling
temperature or setting operation mode is selected and decided by the operation mode given on
the right edge of the table below.
Do not select “timer operation possible by remote control” if not using a remote control.
Operation by timer is impossible in this case.
∗
1. Factory setting
ON by remote
control
(Unified ON by
central remote
control)
OFF by remote
controller
(Unified OFF by
central remote
control)
Temperature
control by
remote control
Operation mode
setting by
remote control
OFF by
remote
control
Control
mode is "1".
Example
↓
Rejection
↓
Rejection
↓
Rejection
↓
Acceptance
↓
Acceptance
(VL069)
Control mode
Control by remote control
Control mode
Operation
OFF
Temperature
control
Operation
mode setting
Unified operation,
individual operation
by central remote
control, or operation
controlled by timer
Unified OFF,
individual stop by
central remote
control, or timer stop
ON/OFF control
impossible by
remote control
Rejection (Example)
Rejection (Example)
Rejection
(Example)
Rejection
Acceptance
0
Rejection
10
Acceptance
(Example)
Acceptance
(Example)
1(Example)
Rejection
11
OFF control only
possible by
remote control
Acceptance
Rejection
Acceptance
2
Rejection
12
Acceptance
Acceptance
3
Rejection
13
Centralized
Acceptance
Rejection
Acceptance
4
Rejection
14
Acceptance
Acceptance
5
Rejection
15
Individual
Acceptance
Rejection
Acceptance
6
Rejection
16
Acceptance
Acceptance
7
∗
1
Rejection
17
Timer operation
possible by
remote control
Acceptance
(During timer at ON
position only)
Acceptance
(During timer at ON
position only)
Rejection
Acceptance
8
Rejection
18
Acceptance
Acceptance
9
Rejection
19
Central remote control
When ON/OFF, temperature setting and
operation mode setting by local remote
control is forbidden, “UNDER CENTRAL
CONTROL” is displayed on the remote
control.