SiEN34-705
Heat Pump 60Hz (RXYQ5~54P)
Installation Manual
275
2. Removing Pinch Piping
!
When connecting refrigerant piping to an outdoor unit, remove the pinch piping.
(Refer to
figure 13)
!
Pinch piping should be removed using the procedure in the figure 13.
Caution:
After removing the gas, remove the pinch piping.
Any gas remaining inside may blow off the pinch piping when you dissolve the brazing, causing
damage.
3. Connecting refrigerant piping to outdoor units
<In case of single system: 5-18HP type>
figure 13
Shutoff valve (liquid side · gas side)
Service port
Pinch piping
Procedure 3:
After removing the gas from the pinch piping,
dissolve the brazing using a burner and
remove the pinch piping.
Procedure 2:
Connect a charge hose to the service port of
the liquid side and gas side shutoff valves and
remove the gas from the pinch piping.
Procedure 1:
Confirm the shutoff valve is closed.
figure 14
If connected to the front
When connected at lateral side (bottom)
Remove the shutoff valve cover to connect.
Gas side shutoff valve
Gas side shutoff valve
Gas side accessory pipe (2)
Gas side piping (field supply)
Brazing
Liquid side shutoff valve
Refrigerant charge port
Liquid side shutoff valve
Refrigerant charge port
Liquid side accessory pipe (2)
Knockout hole
Punch the knock hole.
Liquid side piping (field supply)
Brazing
Brazing
Liquid side accessory pipe (1)
Gas side accessory pipe (1)
Remove the knock hole on the bottom frame and
route the piping under the bottom frame.