Appendix
SiEN34-705
188
General Information
RXQ8PY1
3D055258A
Notes
1. This wiring diagram is applied only to the outdoor unit.
2.
: Field wiring.
3. :
Terminal strip,
: Connector
:Terminal
:Protective earth (screw)
4. When using the optional adapter, refer to the installation manual of the optional adapter.
5. For connection wiring to indoor-outdoor transmission F1 • F2, outdoor-outdoor transmission F1 • F2,
Outdoor-Multi Transmission Q1 • Q2, refer to the installation manual.
6. How to use BS1~5 and DS1~3 switch, refer to “service precaution” label on EL. COMPO. BOX COVER.
7. When operating, don’t shortcircuit the protection device (S1PH).
8. Colors (BLK:Black, RED:red, BLU:blue, WHT:white, PNK:Pink, YLW:Yellow, BRN:brown, GRY:gray, GRN:green,
ORG:0range.
(BACK)
(FRONT)
EL.COMPO.BOX
EL.COMPO.BOX
TERMINAL OF M1C
LAYOUT OF M1C, M1F
OUTER SHELL
Outdoor (F1) (F2)
NOTE 5
TO IN/D UNIT
TO OUT/D UNIT
POWER SUPPLY
Indoor (F1) (F2)
Printed circuit board (Main)
Printed circuit board (Noise filter)
Printed circuit board (INV)
Printed circuit board (FAN)
Printed circuit board (ABC I/P)
Push button switch
(Mode, set, return, test, reset)
Capacitor
Capacitor
DIP switch
Crankcase heater
Fuse (8A, DC650V) (A4P)
Fuse (T, 3.15A, 250V) (A1P)
Fuse (T, 6.3A, 250V) (A2P)
Pilotlamp (Service monitor-orange)
[H2P] Prepare, test ---------------Flickering
Malfunction detection---Light up
Pilotlamp (Service monitor-green)
Magnetic relay
Magnetic contactor (M1C)
Magnetic relay (Y1S)
A1P
A2P
A3P
A4P
A5P
BS1~5
C1
C63,C66
DS1,DS2
E1HC
F1U
F1U,F2U
F400U
H1P~8P
HAP
K1,K3
K2,K4
K3R
L3-BLK
L2-WHT
L1-RED
N-BLU
Magnetic relay (Y2S)
Magnetic relay (Y3S)
Magnetic relay (E1HC)
Reactor
Motor (Compressor)
Motor (Fan)
Switching power supply (A1P,A3P)
Phase reversal detect circuit
Resistor (Current sensor) (A4P)
Resistor
Resistor (Current limiting)
Thermistor (Air) (A1P)
Thermistor (Fin) (A3P)
Thermistor (Suction)
Thermistor (M1C discharge)
Thermistor (Heat exc. deicer)
Thermistor (Heat exc. outlet)
Thermistor (Liq. pipe)
Thermistor (Accumulator)
Pressure sensor (High)
Pressure sensor (Low)
K4R
K5R
K7R
L1R
M1C
M1F
PS
Q1RP
R10
R50, R59
R95
R1T
R1T
R2T
R3T
R4T
R5T
R6T
R7T
S1NPH
S1NPL
Pressure switch (high)
Safety devices input
Power module (A3P,A4P)
Diode bridge (A3P)
Connector (M1F)
Terminal strip (Power supply)
Terminal strip (Control) (A1P)
Electronic expansion valve (Main)
Electronic expansion valve (Subcool)
Solenoid valve (Hot gas)
Solenoid valve (Oil)
Solenoid valve (4 way valve)
Noise filter (Ferrite core)
Noise filter (With surge absorber)
S1PH
V1CP
V1R
V2R
X1A, X2A
X1M
X1M
Y1E
Y2E
Y1S
Y2S
Y3S
Z1C~5C
Z1F
NOTE 4
TO MULTI UNIT
Outdoor (Q1) (Q2)
Содержание RXYQ5PY1
Страница 2: ......
Страница 287: ...SiEN34 705 Heat Pump 60Hz RXYQ5 54P Installation Manual 281...
Страница 292: ...Heat Pump 60Hz RXYQ5 54P SiEN34 705 286 Installation Manual...
Страница 339: ...Operation Manual SiEN34 705 332 Operation Manual...