7.7 Size of Main Gas and Liquid Pipes and Allowable Length
7.7.1 Heat Pump 50Hz/60Hz, Cooling Only 50Hz (RX(Y)Q5~54P, 50PH)
∗
Note 1
When the equivalent pipe length between outdoor and indoor units is 90m or more, the size of main pipes
(both gas-side and liquid-side) must be increased.
Depending on the length of the piping, the capacity may drop, but even in such case it is able to increase the size of main
pipes.
Diameter of above case
Model
Gas
Liquid
RX(Y)Q5 Type
φ
19.1
φ
12.7
RX(Y)Q8 Type
φ
22.2
φ
25.4*
φ
12.7
RX(Y)Q10 Type
φ
15.9
RX(Y)Q12 Type
φ
15.9
RX(Y)Q14 Type
RX(Y)Q16 Type
φ
31.8*
φ
15.9
RX(Y)Q18 Type
φ
31.8*
φ
19.1
RX(Y)Q34 Type
RX(Y)Q36 Type
RX(Y)Q38 Type
RX(Y)Q40 Type
Model
Gas
Liquid
φ
38.1*
φ
22.2
φ
22.2
φ
22.2
φ
22.2
RX(Y)Q42 Type
RX(Y)Q44 Type
φ
22.2
φ
22.2
RX(Y)Q46 Type
φ
22.2
*If available on the site, use this size.
Otherwise, it can not be increased.
RX(Y)Q48 Type
RX(Y)Q50 Type
RX(Y)Q52 Type
RX(Y)Q54 Type
Model
Gas
Liquid
φ
22.2
φ
22.2
φ
22.2
φ
22.2
RX(Y)Q20 Type
RX(Y)Q22 Type
RX(Y)Q24 Type
RX(Y)Q26 Type
RX(Y)Q28 Type
Model
Gas
Liquid
φ
31.8*
φ
19.1
φ
31.8*
φ
19.1
φ
19.1
φ
38.1*
φ
22.2
φ
38.1*
φ
22.2
RX(Y)Q30 Type
φ
38.1*
φ
22.2
RX(Y)Q32 Type
φ
38.1*
φ
22.2
Increase
Indoor unit
The first refrigerant branch kit
Main pipes
Outdoor unit
Not
Increased
Not
Increased
Not
Increased
Not
Increased
Not
Increased
Not
Increased
Not
Increased
Not
Increased
Not
Increased
Not
Increased
Not
Increased
Not
Increased
Not
Increased
Not
Increased