Appendix
SiEN34-705
146
General Information
When istalling this kit, please apply the
following restrictions
To the piping installer
Restrictions on Installing Multi Connection Piping Kit
•
Install the joint horizontally so that the caution label attached to joint comes to the top.
Do not tilt the joint more than
±
15°. (See Fig. 1). In addition, do not install the joint vertically. (See Fig. 2)
•
Make sure the piping up to the joint is straight for more than 500mm. Do not bend the field piping within this range. If a straight field piping
more than 120mm is connected, more than 500mm of straight section can be ensured. (See Fig. 3)
•
Improper installation may lead to malfunction os the outdoor unit.
Installation examples
•
The figure at the lower shows a typical front connection. Make sure to follow the installation restrictions and
carry out installation taking the field requirements into consideration.
•
This manual explains the front connection <Ex. of construction 1>.
•
For 3-unit installation on Ex. of construction 5 and 6, in some cases the reducers (5), (6) or (10) for gas piping
and the reducers (2) and (3) for liquid piping may be used on the 1ste joint (section shown with ).
See the figure at the right for details of connection.
•
When the size of the Gas-side pipe between the Gas-side joint (1) and Gas-side joint (2) on the 3-units system
or the size of the main pipe is
Ø
41.3 or
Ø
34.9. Gas-side reducer (7), (8) and (9) will be used. See the figure at
the right for details of connection.
•
When the size of the Liquid-side pipe between the Liquid-side joint (1) and Liquid-side joint (2) on the 3-units
system is
Ø
12.7. Liquid-side reducer (3) will be used. And when the side of main pipe is
Ø
15.9. Liquid-side
reducer (4) will be used. See the figure at the right for details of connection.
Fig 1
Caution label
Fig 2
Caution label
Max.
±
15°
Fig 3
Ground
Ground
Horizontal
line
More than 500mm of
straight section
Field piping
(More than 120mm
of length
View
⺑
View
⺒
Ex. of
construction
1
Ex. of
construction
2
Ex. of
construction
3
Ex. of
construction
4
Ex. of
construction
5
Ex. of
construction
6
Field
piping
(
Ø
34.9)
Field
piping
(
Ø
41.3)
Field
piping
(
Ø
41.3)
Field
piping
(
Ø
34.9)
Field piping
(
Ø
12.7)
Field piping
(
Ø
15.9)
Field piping
(
Ø
12.7)
Field piping
(
Ø
15.9)
Gas-side
reducer (
7
)
Gas-side
reducer (
9
)
Gas-side
reducer (
7
)
Gas-side
reducer (
7
)
Gas-side
joint
Gas-side joint (1)
Gas-side joint (7)
or Gas-side reducer (9)
Field piping (
Ø
34.9)
or Field piping (
Ø
41.3)
Gas-side reducer (7)
or Gas-side reducer (9)
Gas-side joint (2)
Liquid side
reducer (5)
Liquid side
joint
Cut in the center of
connection area by
pipe cutter
Liquid-side
joint (2)
To outdoor unit
(
Ø
9.5 or
Ø
12.7)
ID Ø 38.1
Liquid side
reducer (3)
ID Ø 31.8
ID Ø 38.1
ID Ø 38.1
Liquid side
joint (3)
Liquid side
reducer (3)
Liquid side
reducer (4)
Cut in the center of connection
area by pipe cutter
Cut in the center of
connection area by
pipe cutter
Cut in the center of
connection area by
pipe cutter
To outdoor unit (
Ø
22.2)
Gas-side reducer (6)
To outdoor unit (
Ø
19.1)
Gas-side reducer (10)
Gas side
joint (1)
Gas side
1ste joint)
Gas side
reducer (5)
Liquid-side reducer (3)
To 2nd joint
To 2nd joint
Liquid-side
reducer (2)
Liquid-side joint (1)
Liquid-side
(1ste joint)
FOR BHFP22P100
FOR BHFP22P151