SiEN34-705
Test Operation
General Information
113
'
Set Cool / Heat for More Than One Outdoor Unit System Simultaneously in
Accordance with Unified Master Outdoor Unit by Indoor Unit Remote Control
$
Install the external control adapter for outdoor unit on either the outdoor-outdoor, indoor-
outdoor transmission line.
$
Set outdoor unit PC board DS1-1 to IN (factory set).
$
In setting mode 1, set the outdoor unit you want to give cool/heat selection permission to as
the group master, and set the other outdoor units as group slave units.
$
Set the outdoor unit external control adapter SS1 to BOTH (factory set) or C/H, and SS2 to
OFF (factory set).
Multi outdoor units connection
I-O
O-O
A
B
C
F1
F2
F1
F2
Q1
Q2
H3P
H4P
H5P
MODE
DEMAND
C/H SELECT
MASTER
IND
OUT
SLAVE
IN
C/H SELECT R.C.
C/H SELECT
OUT-MULTI
CN24
TEST
L.N.O
.P
.
To indoor unit
<Master unit>
DS1-1
To indoor unit
I-O
O-O
A
B
C
F1
F2
F1
F2
Q1
Q2
H3P
H4P
H5P
MODE
DEMAND
C/H SELECT
MASTER
IND
OUT
SLAVE
IN
C/H SELECT R.C.
C/H SELECT
OUT-MULTI
TEST
L.N.O
.P
.
I-O
O-O
A
B
C
F1
F2
F1
F2
Q1
Q2
H3P
H4P
H5P
MODE
DEMAND
C/H SELECT
MASTER
IND
OUT
SLAVE
IN
C/H SELECT R.C.
C/H SELECT
OUT-MULTI
TEST
L.N.O
.P
.
MUL
TI
I-O
O-O
A
B
C
F1
F2
F1
F2
Q1
Q2
H3P
H4P
H5P
MODE
DEMAND
C/H SELECT
MASTER
IND
OUT
SLAVE
IN
C/H SELECT R.C.
C/H SELECT
OUT-MULTI
TEST
L.N.O
.P
.
MUL
TI
To indoor unit
External control adaptor for outdoor unit
SS2
Central
C/H
Selector
OFF ON
BOTH
C/H
DE
FUNCTION
SS1
F1
F2
N
P
DS1
DS2
CENTRAL
NO
TERMINAL
ADDRESS
C/H
<Slave unit>