Installation
General Information
71
3.2.10 Electrical Work
Control Wiring
1. Compatible types of wire
Wiring Specifications
Notes:
1. Sheathed wire may be used for transmission wirings, but they do not comply with EMI
(Electromagnetic lnterference) (EN55014). When using sheathed wire. EMI must conform to
Japanese standards stipulated in the Electric Appliance Regulatory Act. (If using a sheathed
wire, the grounding shown in the figure on the left is unnecessary.)
2. For FXYAP indoor unit, use sheathed wire.
2. Problems arising from the use of unsuitable cable
a) When cable less than 0.75 mm² is used
Where the control wiring is particularly long the transmission signals may, for example,
become unstable and the terminal relay cease to function. (Reduced voltage) The control
system may become unduly subject to noise interference.
b) When cable more than 1.25 mm² is used
When wiring indoor units together, the terminal block will not be able to accommodate 2
cables simultaneously if the cables are larger than 1.25 mm².
c) For multi-core cable
The greater play between wires, the more the transmitted wave is distorted and transmission
destabilized.
d) In the case of a remote control with a three way selector for cooling, heating and ventilation,
twin core cable should be used when the ventilation mode is not required and three core
cable should be used when three way selection is required.
e) Since there is a considerable risk of mixing high (220 to 240V) and low voltage in the case
of, for example, a PCB for remote control, multiple core cable must not be used.
(Internal wiring regulations and dielectric strengths of cables are relevant here.)
f) Other important points
1. The refrigerant circuit and the indoor/outdoor connecting cables must correspond exactly.
2. A suitable gap must be left between the control cables and the power supply cables where
these are laid alongside each other. (See “Separation of control and power supply cables”
on page 73)
Wiring Type
Shield Wire (2 wire) (See NOTE 1, 2)
Size
0.75~1.25 mm²
[Example of incorrect method]
[Example of correct method]
Operate/stop
(6 core cable)
PCB for
Remote
Control
PCB for
Remote
Control
Operate/stop