SiEN34-705
Appendix
General Information
159
2-1 Cutting the field supply gas pipe 1 and 2 and the Gas-side
accessory pipe (3) attached to the outdoor unit
CAUTION
• Cut the pipes according to Table 8 or 9.
• The “L” dimension of the gas pipe 1 in Table 8 and the gas pipe 2 in Table 9 are identical to the “B” dimensions in table 2, those of “field supply elbows”
shown in the procedure of front connection, which are equivalent to “straight size joint” without stopper. If the “B” dimensions are not identical to table
2 or “straight size joint” is with stopper, adjust them as table 2,8 and 9 show.
Connection of gas and liquid pipes
Model
type
8HP
10HP
12HP
~
18HP
Gas-side accessory pipe (3)
B (mm)
dimensions
For 100
For 139
For 233
102 63 48
72
33
25
0
53
0
(no cutting)
(no cutting)
Table 8 (For outdoor unit A, B Side)
cutting position
unnecesary
Gas-pipe 1 (field supply)
L (mm)
dimensions
For 100 For 139 For 233
79
86
92 133
Table 9 (For outdoor unit C Side)
Model
type
8HP
10HP
12HP
~
18HP
Gas-side accessory pipe (3)
B (mm)
dimensions
For 100
For 139
For 233
0 0 0
(no cutting)
(no cutting)
(no cutting)
18
0
0
(no cutting)
(no cutting)
32
0
0
(no cutting)
(no cutting)
cutting position
Gas-pipe 2 (field supply)
L (mm)
dimensions
For 100 For 139 For 233
76
115 209
88
109 203
96
103 197
Liquid-side reducer
Gas-side joint
Liquid-side joint
Ground
Max.
+ 15°
Max.
+ 15°
View
2-2 Connection of pipes
CAUTION
• Remove the knockout plate on the bottom frame. (See the installation manual attached to the outdoor unit)
• Connect the gas and liquid pipe as shown in the figure below. (When connecting the pipes, first connect the gas-side joint and the gas-side
reducer (1), the liquid-side joint and the liquid-side reducer (1)).
• See the caution section in the installation manual attached to the outdoor unit for brazing pipes and connecting pipes with flare nuts.
• Install the joint in such a way that the attached face of the caution label becomes horizontal. (See the view A)
• Connect the liquid side reducer (1) tilting approx. 10° and bend the field supplied liquid pipe up to the stop valve as shown in the figure below.
(See the view A)
• If the liquid side reducer is connected vertically without bending the liquid pipes, the insulation will not fit.
Gas-side accessory pipe (3)
(Attached to the outdoor unit)
Gas-side reducer (1)
Gas-side reducer (3)
Gas-side reducer (1)
Gas-side reducer (4)
Liquid-side reducer (1)
Liquid-side reducer (1)
Gas-side joint (1)
Liquid-side joint (1)
Gas-side joint (2)
Liquid-side joint (2)
Liquid pipe
(field supply)
Gas pipe (field supply)
(select the pipe length on site)
Gas pipe (field supply)
(select the pipe length on site)
straight size joint
(field supply)
straight size joint
(field supply)
straight size joint
(field supply)
Outdoor
unit A
Outdoor
unit B
Outdoor
unit C
Elbow (field supply)
Gas pipe 2
(field supply)
(As per Table 9)
Gas pipe 1 (field supply)
(As per Table 8)
The work after the kit is connected
Connection of piping between the outdoor unit and the indoor unit
Air tight test
Insulation of joints
• See “The work after the kit is connected” for a front connection in “BHFP22P100 Installation Instructions.”
Follow the instructions in the installation manual included with the outdoor unit,
when performing installation work.