Test Operation
General Information
105
No.
Setting item
Description
0
Digital pressure
gauge kit display
Used to make setting of contents to display on the digital
pressure gauges (e.g. pressure sensors and temperature
sensors)
1
Cool/heat unified
address
Sets address for cool/heat unified operation.
2
Low noise/demand
address
Address for low noise/demand operation
3
Test operation
settings
Used to conduct test operation without making changes
to the PCB and replacing the refrigerant, after the
completion of maintenance.
5
Indoor unit forced
fan H
Allows forced operation of indoor unit fan while unit is
stopped. (H tap)
6
Indoor unit forced
operation
Allows forced operation of indoor unit.
8
Te setting
Target evaporation temperature for cooling
9
Tc setting
Target condensation temperature for heating
10 Defrost changeover
setting
Changes the temperature condition for defrost and sets to
quick defrost or slow defrost.
11 Sequential
operation setting
Sets sequential operation
(Factory set to ON)
12
External low noise
setting / Demand
setting
Reception of external low noise or demand signal
13 AIRNET address
Set address for AIRNET.
16 Setting of hot water Make this setting to conduct heating operation with hot
water heater.
18 High static pressure
setting
Make this setting in the case of operating in high static
pressure mode with diffuser duct mounted.
(In order to mount the diffuser duct, remove the cover
from the outdoor unit fan.)
19
Emergency
operation
(STD compressor
operation
prohibited)
Used to operate system only with inverter compressor
when STD compressor malfunctions. This is a temporary
operation extremely impairing comfortable environment.
Therefore, prompt replacement of the compressor is
required.
(This operation, however, is not set with RXYQ5, 8P.)
20
Additional
refrigerant charge
operation setting
Carries out additional refrigerant charge operation.
21
Refrigerant recovery/
vacuuming mode
setting
Sets to refrigerant recovery or vacuuming mode.
22 Night-time low
noise setting
Sets automatic nighttime low noise operation in a simple
way.
The operating time is based on “Starting set” and “Ending
set”.
24 ENECUT test
operation
Used to forcedly turn ON the ENECUT. (Be noted that the
ENECUT is only functional with outdoor unit in the
stopped state - Japanese domestic model only.)
25 Setting of external
low noise level
Sets low noise level when the low noise signal is input
from outside.
26
Night-time low
noise operation
start setting
Sets starting time of nighttime low noise operation.
(Night-time low noise setting is also required.)
27
Night-time low
noise operation end
setting
Sets ending time of nighttime low noise operation.
(Night-time low noise setting is also required.)
28
Power transistor
check mode
∗
Check after
disconnection of
compressor wires
Used for trouble diagnosis of DC compressor. Since the
waveform of inverter is output without wiring to the
compressor, it is convenient to probe whether the trouble
comes from the compressor or PC board.
29 Capacity
precedence setting
If the capacity control is required, the low noise control is
automatically released by this setting during carrying out
low noise operation and nighttime low noise operation.
(V2764)
b. “Setting mode 2”
Push and hold the MODE (BS1)
button for 5 seconds and set to
“Setting mode 2”.
Push the SET (BS2) button and set
to the setting condition you want.
↓
Push the RETURN (BS3) button and
decide the condition.
<Selection of setting items>
<Selection of setting conditions>
Push the SET (BS2) button and set
the LED display to a setting item
shown in the table on the right.
↓
Push the RETURN (BS3) button and
decide the item. (The present setting
condition is blinked.)
Push the RETURN (BS3) button and
set to the initial status of “Setting
mode 2”
∗
If you become unsure of how to
proceed, push the MODE (BS1)
button and return to setting mode 1.