SiEN34-705
Test Operation
General Information
123
4.4.2.6 Check Operation Detail.
Unit stopping
Press the TEST button for 5 seconds.
10 sec to 10 minutes
LED display (H1P~H7P) (
8
:
ON
3
:
OFF
9
:
BLINK)
3383333
3933338
Pressure equalizing
Step 1
20 sec to 2 minutes
10 minutes
5 minutes
3933383
Cooling start control
Step 2
3933388
3938338
3938383
Stability waiting operation
Step 3
Pump down residual operation
Step 9
5 minutes
Standby for restarting
Completion
Step 10
•
Stop valve close check
•
Wrong wiring check
•
Correct Refrigerant charge check
•
Piping length check
3933833
3933838
3933883
3933888
3938333
Judgement function
Step4~8
CHECK OPERATION FUNCTION
(Press the MODE button BS1 once and set to SETTING MODE 1 (H1P: OFF))