SiEN34-705
Heat Pump 60Hz (RXYQ5~54P)
Installation Manual
293
2.7.6 Procedure for Wiring Inside Units
!
Referring to figure 27, secure and wire the power and transmission wiring using the included
clamp (1), (2), and (3).
Caution:
!
The transmission wiring must be at least 50 mm away from the power wiring.
!
Make sure all wiring do not contact to the pipes (hatching parts in the figure 27).
!
After wiring work is completed, check to make sure there are no loose connections among
the electrical parts in the EL.COMPO.BOX.
[In case of 5~10HP type]
[In case of 12~18HP type]
Electric conduit
Electric conduit
Transmission wiring
Transmission wiring
Ground
wire
Ground
wire
Retain with accessory
clamp (3).
When routing out the transmission
wiring from the opening for piping.
When routing out the
power/ground wires
from the left side.
When routing out the
transmission wiring from
the knockout hole.
Retain to the back of
the column support
with the accessory
clamp (2).
Clear over
50 mm.
When routing out the power/
ground wires from the front.
When routing out the
power/ground wires from
the right side.
Power
wiring
Retain with
accessory
clamp (3).
Secure to the back
side of the support
beam using the
accessory clamp (1).
When routing out the
power/ground wires from
the left side.
When wiring, exercise sufficient
caution not to detach the acoustic
insulators from the compressor.
Retain to the
back of the
column
support with
the accessory
clamp (2).
When routing out
the power/ground
wires from the front.
Clear over
50 mm.
When routing out the
transmission wiring from
the knockout hole.
Retain to the back of
the column support
with the accessory
clamp (2).
When routing out the
power/ground wires
from the right side.
When routing out
the transmission
wiring from the
opening for piping.
Power
wiring
figure 27
Содержание RXYQ5PY1
Страница 2: ......
Страница 287: ...SiEN34 705 Heat Pump 60Hz RXYQ5 54P Installation Manual 281...
Страница 292: ...Heat Pump 60Hz RXYQ5 54P SiEN34 705 286 Installation Manual...
Страница 339: ...Operation Manual SiEN34 705 332 Operation Manual...