Heat Pump / Cooling Only 50Hz (RX(Y)Q5~54P)
SiEN34-705
236
Installation Manual
3.6.6 E
XAMPLE
OF
C
ONNECTION
)
∗
Note 1
When the equivalent pipe length between outdoor and indoor units is 90m or more, the size of main pip
Depending on the length of the piping, the capacity may drop, but even in such case it is able to increa
∗
Note 2
Allowable length after the first refrigerant branch kit to indoor units is 40 m or less, however it can be extend
∗
Note 3
If the pipe size above the REFNET header is
φ
34.9 or more, KHRP26M73HP is required.
Diameter of above case
Model
Gas
Liquid
RX(Y)Q5 Type
φ
19.1
φ
12.7
RX(Y)Q8 Type
φ
22.2
φ
25.4*
φ
12.7
RX(Y)Q10 Type
φ
15.9
RX(Y)Q12 Type
φ
15.9
RX(Y)Q14 Type
RX(Y)Q16 Type
RX(Y)Q20 Type
RX(Y)Q22 Type
RX(Y)Q24 Type
RX(Y)Q26 Type
RX(Y)Q28 Type
φ
31.8*
φ
15.9
RX(Y)Q18 Type
φ
31.8*
φ
19.1
Model
Gas
Liquid
φ
31.8*
φ
19.1
φ
31.8*
φ
19.1
φ
19.1
φ
38.1*
φ
22.2
φ
38.1*
φ
22.2
RX(Y)Q30 Type
φ
38.1*
φ
22.2
RX(Y)Q32 Type
φ
38.1*
φ
22.2
*If available on the site, use this size. Otherwise it can not be increased.
Required Conditions
Example Drawings
1. It is necessary to increase the pipe size between the first branch
kit and the final branch kit. (Reducers must be procured on site)
However, the pipes that are same pipe size with main pipe must
not be increased.
2. For calculation of Total extension length, the actual
length of above pipes must be doubled. (except
main pipe and the pipes that are not increased)
3. Indoor unit to the nearest branch kit
≤
40 m
4. The difference between
[Outdoor unit to the farthest indoor unit] and [Outdoor
unit to the nearest indoor unit]
≤
40 m
8 b + c + d + e + f + g + p
≤
90 m
increase the pipe size of b, c, d, e, f
a + b × 2 + c × 2 + d × 2 + e × 2 + f × 2 + g
+ h + i + j + k + l + m + n + p
≤
1000 m
h, i, j....... p
≤
40 m
The farthest indoor unit 8
The nearest indoor unit 1
( a + b + c + d + e + f + g + p ) - ( a + h )
≤
4
figure 9
Outdoor unit
Increase
The first refrigerant branch kit
Indoor unit
Main pipes
Not
Increased
Not
Increased
Not
Increased
Not
Increased
Содержание RXYQ5PY1
Страница 2: ......
Страница 287: ...SiEN34 705 Heat Pump 60Hz RXYQ5 54P Installation Manual 281...
Страница 292: ...Heat Pump 60Hz RXYQ5 54P SiEN34 705 286 Installation Manual...
Страница 339: ...Operation Manual SiEN34 705 332 Operation Manual...