Appendix
SiEN34-705
168
General Information
During operation
(V1093)
Inspection item
Inspection method
Standard (guideline)
Measurement values
Decision
Ou
td
oor unit 1
Main power supply voltage
Tester
Rated voltage ±10%
R-S V S-T V R-T
V
Operation circuit voltage Tester
Rated voltage ±10%
V
Fan rotation direction Visual inspection Forward rotation
G NG
Fan noise/vibration Listening
No noise or vibration
Fan operation current
Clamp meter
RED WHITE BLACK
A A A
Suction air temperature
Thermometer
Temperature differential
9~11deg. when cooling,
2~3.5deg. when heating
°C
Discharge air temperature
Thermometer
°C
Compressor discharge pressure Pressure gauge
MPa
Compressor suction pressure
Pressure gauge
MPa
Compressor operating current
Clamp meter
Phase differential
within 1A
INV
U( )A,
V( )A,
W( )A
STD1
R( )A,
S( )A,
T( )A
STD2
R( )A,
S( )A,
T( )A
Compressor operating frequency Clamp meter
INV
Hz
Suction pipe temperature
Thermometer
3~15°C
INV °C STD1 °C STD2 °C
Discharge pipe temperature Thermometer
85~105°C
INV °C STD1 °C STD2 °C
Clank case heater
Touch
Warm
INV G·NG STD1 G·NG STD2 G·NG
Outd
oor uni
t 2
Main power supply voltage
Tester
Rated voltage ±10%
R-S V
R-S V
R-S
V
Operation circuit voltage Tester
Rated voltage ±10%
V
Fan rotation direction Visual inspection Forward rotation
G NG
Fan noise/vibration Listening
No noise or vibration
Fan operation current
Clamp meter
RED WHITE BLACK
A A A
Suction air temperature
Thermometer
Temperature differential
9~11deg. when cooling,
2~3.5deg. when heating
°C
Discharge air temperature
Thermometer
°C
Compressor discharge pressure Pressure gauge
MPa
Compressor suction pressure
Pressure gauge
MPa
Compressor operating current
Clamp meter
Phase differential
within 1A
INV
U( )A,
V( )A,
W( )A
STD1
R( )A,
S( )A,
T( )A
STD2
R( )A,
S( )A,
T( )A
Compressor operating frequency Clamp meter
INV
Hz
Suction pipe temperature
Thermometer
3~15°C
INV °C STD1 °C STD2 °C
Discharge pipe temperature Thermometer
85~105°C
INV °C STD1 °C STD2 °C
Clank case heater
Touch
Warm
INV G·NG STD1
G·NG STD2 G·NG
Outdoo
r un
it
3
Main power supply voltage
Tester
Rated voltage ±10%
R-S V
R-S V
R-S
V
Operation circuit voltage Tester
Rated voltage ±10%
V
Fan rotation direction Visual inspection Forward rotation
G NG
Fan noise/vibration Listening
No noise or vibration
Fan operation current
Clamp meter
RED WHITE BLACK
A A A
Suction air temperature
Thermometer
Temperature differential
9~11deg. when cooling,
2~3.5deg. when heating
°C
Discharge air temperature
Thermometer
°C
Compressor discharge pressure Pressure gauge
MPa
Compressor suction pressure
Pressure gauge
MPa
Compressor operating current
Clamp meter
Phase differential
within 1A
INV
U( )A,
V( )A,
W( )A
STD1
R( )A,
S( )A,
T( )A
STD2
R( )A,
S( )A,
T( )A
Compressor operating frequency Clamp meter
INV
Hz
Suction pipe temperature
Thermometer
3~15°C
INV °C STD1 °C STD2 °C
Discharge pipe temperature Thermometer
85~105°C
INV °C STD1 °C STD2 °C
Clank case heater
Touch
Warm
NV G·NG STD1 G·NG STD2 G·NG