SiEN34-705
Installation
General Information
81
3P170269B
Check the system status on LED(H2P) on the Pc board (A1P) from
inspection door on the EL, COMPO, BOX cover
LED display shows:
TURNING OFF***Normal TURNING ON***Abnormal
FLASHING***Under preparation
(For multi system, check the PC board of the master unit. The master unit
is the outdoor unit connected to the transmission wiring to the indoor units.)
To Service Person
●
Beware the fan running when inspect.
●
Do not touch the charged parts when inspect
To ALL handlers
●
For removing the front panel, lift the panel a little (
①
), and pull
the panel towards you (
➁
).
●
For the location of the EL, COMPO. BOX and the service port,
see as shown below on the right.
Hanging lug
Front panel
EL. COMPO. BOX
Wiring diagram
(On the back
side of the
cover)
Inspection door
Earth terminal
(Inside the EL. COMPO. BOX)
Gas shutoff valve
service port
(Cooling-low pressure
Heating-high pressure)
Liquid shutoff valve
service port
(Cooling-high pressure
Heating-intermediate
pressure)
Refrigerant
charging port
(Heating-low pressure)
WARNING Caution to electric shock
.
3P173367B
●
Do not remove the cover by force. If the cover is deformed,
water may enter inside, wich may cause failure.
●
Install the cover so that the sealing material labeled on the lower
part on its back side may not get caught in the EL. COMPO.
BOX inside. (See as shown below)
CAUTION for removing and installing the EL. COMPO. BOX cover
Method of removal
CAUTION
Method of installation
WARNING Caution to electric shock
➀
Remove the 4 screws fixing the cover.
➁
Pull the cover downward till its top shows.
➂
Pull the cover frontward and remove it.
For installing the cover, follow the
procedures in the reverse order.
Shut off the power supply before removing the cover.
If your fingers thouch the electrical components it may
cause electric shock.
It cause damp or
water to enter
Power supply
terminal block
EL. COMPO.
BOX cover
Front
side
Sealing material
Sealing material
Do not draw
the lower part
of the cover
Top cover
Содержание RXYQ5PY1
Страница 2: ......
Страница 287: ...SiEN34 705 Heat Pump 60Hz RXYQ5 54P Installation Manual 281...
Страница 292: ...Heat Pump 60Hz RXYQ5 54P SiEN34 705 286 Installation Manual...
Страница 339: ...Operation Manual SiEN34 705 332 Operation Manual...