Appendix
SiEN34-705
140
General Information
Piping between refrigerant branch kits
!
Choose from the following table in accordance with the total capacity index of all the indoor
units connected below this.
!
Do not let the connection piping exceed the main refrigerant piping size.
(Unit:mm)
Piping between refrigerant branch kit and indoor unit
!
Match to the size of the connection piping on the indoor unit.
(Unit:mm)
Indoor unit total capacity index
Piping size (O.D.)
Gas pipe
Liquid pipe
< 150
φ
15.9
φ
9.5
150
≤
x< 200
φ
19.1
200
≤
x< 290
φ
22.2
290
≤
x< 420
φ
28.6
φ
12.7
420
≤
x< 640
φ
15.9
640
≤
x< 920
φ
34.9
φ
19.1
920 ≤
φ
41.3
Indoor unit capacity type
Piping size (O.D.)
Gas pipe
Liquid pipe
20 · 25 · 32 · 40· 50 type
φ
12.7
φ
6.4
63 · 80 · 100 · 125 type
φ
15.9
φ
9.5
200 type
φ
19.1
250 type
φ
22.2