Test Operation
SiEN34-705
96
General Information
4.4.1.7 Outdoor Air Processing Unit-Field Setting (Remote Control)
Note) Bold face in
indicates the default setting.
Mode
No.
Setting
SW
No.
Setting
contents
Setting position No.
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
10
(20)
0
Stain of filter
2500hr
1250hr
—
—
—
—
—
—
—
—
—
—
—
—
—
3
Filtering
time
cumulation
Display
No
display
—
—
—
—
—
—
—
—
—
—
—
—
—
12
(22)
1
External
ON/OFF
input
Forced
stop
ON-OFF
control
—
—
—
—
—
—
—
—
—
—
—
—
—
5
Power
failure
automatic
reset
Not
equipped Equipped
—
—
—
—
—
—
—
—
—
—
—
—
—
14
(24)
3
Discharge
temperature
(cooling)
13°C
14
15
16
17
18
19
20
21
22
23
24
25
25
25
4
Discharge
temperature
(heating)
18°C
19
20
21
22
23
24
25
26
27
28
29
30
30
30