Controllers
Parameter manual
b maXX
BM3000
Document no.: 5.12001.07
Baumüller Nürnberg GmbH
518
4.7
4.7.6
Flux controller
The output of the field weakening controller is the set value of the flux controller at asyn-
chronous machines. The flux controller is a simple PI-controller with proportional gain Kp,
integral time Tn and limitation. The Isd-set value is at the output of the flux controller.
The actual flux value is calculated from an asynchronous machine value. If the Kp of the
flux controller is set to 0, the inverse of the Imr-flux-characteristic is set for the Isd-set val-
ue.
4.7.6.1 ProDrive Flux controller
Figure 172:
ProDrive Flux controller
4.7.6.2 Parameter Overview of the Flux Controller
Functional blocks:
FbAsynchronmaschine [146]
Number
Name
Type
Min
Max
Default Value
Unit
Factor
R
ead o
n
ly
St
o
ra
g
e
D
S
Su
pp
ort
C
yclic W
rite
146.10
Kp flux controller
FLOAT
0
1e9
0
1/s
1:1
X
146.11
Tn flux controller
FLOAT
0
10000
1000
ms
1:1
X
146.12
Limit magnetizing current
FLOAT
0
1e9
10
A
1:1
X
146.15
Actual flux current
FLOAT
-1e9
1e9
0
A
1:1
X
146.18
Integral term flux controller
FLOAT
-1e9
1e9
0
A
1:1
X