Configuration
Parameter manual
b maXX
BM3000
Document no.: 5.12001.07
Baumüller Nürnberg GmbH
108
4.4
175.3
Max. device control cabin temperature
From controller version V01.09. onwards. The parameter is used in the PU temperature
model, only.
Maximally provided or expected temperature change within the control cabinet (for air-
cooled devices) or change of surface temperature of the device (for devices with cold
plate cooling) in °C.
Important for devices, which support the PU temperature model (see status of PU tem-
perature model
), only.
The parameter effects the value of the I
2
t max. continuous current
of the maximum continuous current of the device
.
There is no reduction of the output current at the default value of the parameter. This
means that the default value remains if there is no change of the required operating con-
ditions to be expected.
The parameter can be changed during the inhibited drive status, only.
175.4
Max. device altitude
From controller version V01.09. onwards. The parameter is used in the PU temperature
model, only.
Maximally provided or expected installation altitude in m above sea level.
Important for devices, which support the PU temperature model (see status PU tempera-
ture model
The parameter effects the value of the I
2
t max. continuous current
of the maximum continuous current of the device
.
There is no reduction of the output current at the default value of the parameter. This
means that the default value remains if there is no change of the required operating con-
ditions to be expected.
The parameter can be changed during the inhibited drive status, only
175.5
Max. device mains voltage
From controller version V01.09 onwards. The parameter is used in the PU temperature
model, only.
Maximally provided or expected effective value of power supply in V.
Important for devices, which support the PU temperature model (see status PU tempera-
ture model
The parameter effects the value of the maximum continuous current of the device
There is no reduction of the output current at the default value of the parameter. This
means that the default value remains if there is no change of the required operating con-
ditions to be expected.