Set Value Generators
Parameter manual
b maXX
BM3000
Document no.: 5.12001.07
Baumüller Nürnberg GmbH
416
4.6
Figure 138:
Absolute value of min. / max. input
110.17
Input 32 bit additive
Additional ramp function generator input value with 32 bit resolution.
The additional set value is used independent of the input selection in parameter
bit 5. This additional set value is always added to the defined main set value (
), to a total set value. Subsequent to this, checking is made using the input value
limitation (
).
Standardization:
100%
=
Maximum drive speed (
, [rpm])
110.20
Controlled stop time
Delay ramp for the controlled stop.
The set time in this parameter applies to a 100% change of the set value.
110.21
SS1 stop time
The SS1 stop ramp brakes the drive speed-controlled to 0.
The set time in this parameter applies to a 100% change of the set value (braking decel-
eration independent of the instantaneous speed) or applies to the instantaneous speed
(braking time to 0 independent of the instantaneous speed). The behavior is set in param-
eter
bit 13.
The SS1 stop ramp is available only for error reactions.
110.22
Active cycle time ramp generator
Displaying the cycle time of the set value processing of the ramp function generator.