Set Value Generators
Parameter manual
b maXX
BM3000
Document no.: 5.12001.07
Baumüller Nürnberg GmbH
438
4.6
4.6.6.2 Description of the Parameters
168.1
Status
Status of the Motor potentiometer
168.2
Mode
Operating mode of the Motor potentiometer
Bit no.
Meaning
0
1: Motor potentiometer active
3 … 1
Reserved
4
1: Ramp-up final value at Motor potent reached
5
1: Ramp-down final value at Motor potentiometer- reached
6
1: Button Motor potent depressed
7
1: Button Motor potentiometer- depressed
8
1: Motor potent active
9
1: Motor potentiometer- active
10
1: Error at writing on the target parameter (e.g. value greater than maxi-
mum value)
15 ... 11
Reserved
Bit no.
Meaning
0
0: Disable Motor potentiometer
1: Enable Motor potentiometer
1
0: Motor potent off
1: Motor potent on
2
0: Motor potentiometer- off
1: Motor potentiometer- on
3
Synchronization of the Motor potentiometer- output at activation
0: Output is synchronized to the ramp function generator parameter
Input 16 bit
1: Output is set to 0
4
Evaluation of the Motor potenti/-
0: Edge sensitive
1: Level sensitive
15 … 5
Reserved