Description of the Software Modules and Parameters
Parameter manual
b maXX
BM3000
Document no.: 5.12001.07
367
4
The operation only takes place in the device RAM.
Possible error messages:
n
Data set has already been created
n
Incorrect data set number (not in range 1 to 7)
m
Delete Data Set <n>
This data set command deactivates a data set. The data set specified by
Target
Data Set may not be the immediately active data set. The deactivation has the effect of
preventing the device from switching to the specified data set any more. The parameters
of the deleted data set (the data set parameter only) are set to default values.
Possible error messages:
n
Incorrect data set number (not in range 1 to 7, active data set)
m
Copy Data Set <x> to Data Set <y> (from RAM to RAM)
This data set command copies in RAM the parameters from Data Set x (
Data Set) to the parameters of Data Set y (
Target Data Set). The copying pro-
cedure takes a few milliseconds - for that reason the command is only permitted when the
device is inhibited.
Only source data sets that are already created may be specified. If a target data set that
has not yet been created is specified, it will be created automatically.
Possible error messages:
n
Incorrect source data set number
n
Incorrect target data set number
n
Device is not inhibited
m
Load Data Set <x> from Flash
This data set command loads all the parameters in Data Set x (
Source Data Set)
from Flash memory to the device's working memory. The target data set corresponds to
the source data set. The data set must have been created. In Online mode (operation en-
abled), the data set must not be the immediately active data set. During the copying pro-
cedure, any changeover of the data sets is inhibited.
Possible error messages:
n
Incorrect source data set number
n
Device is not inhibited
n
Value less than minimum value
n
Value greater than maximum value
n
Parameter is read-only
n
Due to operating state, parameter cannot be changed
n
Parameter value is invalid
n
Check yielded faulty checksum
Содержание b maXX BM2500
Страница 740: ...Monitoring Parameter manual b maXX BM3000 Document no 5 12001 07 Baumüller Nürnberg GmbH 740 of 820 4 11 ...
Страница 814: ...Parameter manual b maXX BM3000 Document no 5 12001 07 Baumüller Nürnberg GmbH 814 of 820 ...
Страница 820: ...Parameter manual b maXX BM3000 Document no 5 12001 07 Baumüller Nürnberg GmbH 820 of 820 Notizen ...
Страница 821: ......