Management
Parameter manual
b maXX
BM3000
Document no.: 5.12001.07
Baumüller Nürnberg GmbH
336
4.5
4 SWITCHED ON
OPERATION ENABLED
n
Event:
– Drive activation by control word:
m
"Enable Operation" command
– Drive activation by hardware control inputs:
m
Controller Enable input = High (only if Controller Enable (RF) hardware control in-
put is used)
n
Condition:
– Drive activation by control word:
m
Controller Enable input = High (only if Controller Enable (RF) hardware control in-
put is used)
n
Action:
m
Drive function is enabled
5 OPERATION ENABLED
OPERATION INHIBIT ACTIVE
n
Event:
m
"Inhibit Operation" command or
– Drive activation by hardware control inputs:
m
Controller Enable input = Low (transition only possible if Controller Enable (RF)
hardware control input is used)
n
Action:
m
Operation Inhibit is initiated (braked or coast-down, depending on setting)
5a OPERATION INHIBIT ACTIVE
SWITCHED ON
n
Event:
m
INHIBIT response (P108.15) is set to "Inhibit Drive Function" (Pulse Inhibit, value
0) or
m
Operation Inhibit has ended (speed 0 reached)
n
Action:
m
Drive function is inhibited
6 SWITCHED ON
READY TO SWITCH ON
n
Event:
m
"Shut Down" command or
m
Pulse enable input = Low
n
Action:
m
None
7 READY TO SWITCH ON
SWITCH-ON INHIBIT
n
Event:
m
"Quick Stop" command or
m
"Inhibit Voltage" command or
m
Quick Stop input = Low (only if Quick Stop (SH) hardware control input is used)