Configuration
Parameter manual
b maXX
BM3000
Document no.: 5.12001.07
Baumüller Nürnberg GmbH
106
4.4
130.35
Mains failure detection mode
A mains failure is normally detected by the supply unit.
This detection is not fast enough for specific applications. Therefore the DC link voltage
can be additionally used to determine a mains failure.
Bit no.
Meaning
0
0: No error
1: Timeout.
No update of the status word within the last two seconds.
Bits 5 ... 7 and bits 13 ... 15 are not valid
1
1: CRC error at latest transfer of the status word
4 ... 2
Reserved
5
0: No error
1: Error at internal communication in STO module
6
0: No error
1: Internal diagnosis channel 2 has triggered STO
7
0: No error
1: Internal diagnosis channel 1 has triggered STO
12 ... 8
Reserved
13
0: No error
1: Initialization error in STO module
14
0: Input terminal channel 2 is powered with 24 V
1: No 24 V power supply at input terminal of channel 2
15
0: Input terminal channel 1 is powered with 24 V
1: No 24 V power supply at input terminal of channel 1
Value
Meaning
Remark
0
Mains failure detection via
the supply unit
A mains failure is detected in the supply unit by
means of the mains.
1
Mains failure detection
additionally via DC link volt-
age (relative threshold).
The nominal value of the DC link voltage is
determined after switch on of mains. The
adjustable threshold (
) is related to
this value.
As soon as the DC link voltage falls below this
threshold, this is regarded as mains failure.
2
Mains failure detection
additionally via DC link volt-
age (absolute threshold).
As soon as the DC link voltage falls below the
threshold set in
, this is regarded as
mains failure.