4.7.7.4 Adaption torque monitoring
As shown in
the torque monitoring is dependent of the flux actual value, set
value and the motor torque constant.
Figure 174:
Torque monitoring
with:
Flux set
Flux set value in %.
Flux act
Flux actual value in %.
Kt Kt
=
Kt
corr
· Kt factor, in Nm/A
Kt corr
Kt correction factor
Kt factor
Motor Kt in Nm/A
Isq max
Max. torque current
(to controller FW 01.12) or
Max. torque current actual value
from FW 01.13
Isq act
M max
Max. torque actual value
, in Nm
M act
Torque display
, in Nm
M lim
Torque limit symmetric
Isq set lim
From
internally calculated torque current set value
limit in A
At the ASM the magnetic flux is dependent of the saturation influence (refer to
5000_0347_rev01.cdr
138.20
138.21
-1
Flux act 146.14
100
Flux set 145.13
100
Kt
M act
M max
Isq act, 47.5
Isq max
M lim,138.22
Isq set lim