SIMODRIVE alarms
11/2006
Overview of Alarms
2-807
©
Siemens AG, 2006. All rights reserved
SINUMERIK, SIMODRIVE Diagnostics Manual (DA), 11/2006 Edition
380072
Profibus DP: output slot for base address %1 (size %2) not allowed
Parameters:
%1 = Logical base address of the requested area
%2 = Size of the area in bytes
Definitions:
An incorrect logical base address was set for a digital or analog output, the area is resides in the
access range of the PLC (PIQ, base addresses < 256).
For length =1 it is a digital output,
For length =2 it is an analog output.
Reaction:
Channel not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
Remedy:
Only use addresses >= 256 for output slots.
Enter correct base addresses in the machine data:
- For length=1: Correct machine data MN_HW_ASSIGN_DIG_FASTOUT.
- For length=2: Correct machine data MN_HW_ASSIGN_ANA_FASTOUT.
- NCK restart
If the error cannot be eliminated by this procedure, please make a note of the error text and contact
the control system manufacturer.
Program
Continuation:
Switch control OFF - ON.
380075
PROFIBUS DP: DP I/O failure bus %2 slave %1
Parameters:
%1 = Slave address
%2 = Number of the affected bus
Definitions:
Failure of a PROFIBUS slot used by the NCK for digital or analog I/O.
Reaction:
Alarm display.
Remedy:
Check that the PROFIBUS slave is operating correctly (all slaves must be included in the bus, green
LED).
Program
Continuation:
Alarm display showing cause of alarm disappears. No further operator action necessary.
380500
Profibus-DP: fault on drive %1, code %2, value %3, time %4
Parameters:
%1 = Axis
%2 = Fault code of drive (P824)
%3 = Fault value of drive (P826)
%4 = Fault time of drive (P948/P825)
Definitions:
Contents of fault memory of assigned drive.
Reaction:
Alarm display.
Remedy:
See drive documentation for fault codes/fault values.
Program
Continuation:
Alarm display showing cause of alarm disappears. No further operator action necessary.
380501
PROFIBUS DP: fault on bus,slave,DO-Id %1, code %2, value %3, time %4
Parameters:
%1 = 8 bit bus number, 8 bit slave number, 16 bit DO-ld
%2 = Fault code of drive (P947)
%3 = Fault value of the drive (P949)
%4 = Fault time of the drive (P948)
Definitions:
Contents of the fault memory of the assigned slave.
Reaction:
Alarm display.
Remedy:
See drive documentation for fault codes/fault values.
Program
Continuation:
Alarm display showing cause of alarm disappears. No further operator action necessary.