10656
Channel %1 axis %2 gantry slave axis dynamically overloaded
Parameters:
%1 = Channel number
%2 = Axis
Definitions:
The indicated gantry slave axis is dynamically overloaded, i.e. the slave axis cannot follow the master
axis dynamically
Reaction:
Mode group not ready.
Local alarm reaction.
Channel not ready.
Interface signals are set.
Alarm display.
Remedy:
Please inform the authorized personnel/service department. Compare the axial machine data of the
gantry slave axis with the data of the gantry master axis
Program
Continuation:
Clear alarm with the RESET key in all channels of this mode group. Restart part program.
10657
Channel %1 axis %2 power OFF in the gantry error limit exceeded status
Parameters:
%1 = Channel number
%2 = Axis
Definitions:
Gantry error limit exceeded status (alarm 10653) has been switched off.
The error can only be removed by deleting MD GANTRY_ACT_POS_TOL_ERROR or by
deactivating the extended monitoring (MD GANTRY_FUNCTION_MASK Bit0).
Reaction:
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy:
Please inform authorized personnel / the service department.
1. Remove a mechanical misalignment
2. Check axis (uneven mechanical movement?)
3. Delete MD GANTRY_ACT_POS_TOL_ERROR or deactivate the extended monitoring
4. MD 37120 GANTRY_POS_TOL_ERROR is set incorrectly
If the MD is changed, a power ON will be required.
Program
Continuation:
Clear alarm with the RESET key. Restart part program