NCK alarms
11/2006
Overview of Alarms
2-277
©
Siemens AG, 2006. All rights reserved
SINUMERIK, SIMODRIVE Diagnostics Manual (DA), 11/2006 Edition
15910
Channel %1 block %2 touch probe not allowed
Parameters:
%1 = Channel number
%2 = Block number, label
Definitions:
Measure without deletion of distance-to-go
In the part program, an illegal probe has been programmed with the command MEAW (measure
without distance-to-go). The probe numbers
0 ... no probe
1 ... probe 1
2 ... probe 2
are allowed, whether the probe is actually connected or not.
Example:
N10 MEAW=2 G01 X100 Y200 Z300 F1000
Probe 2 without deletion of distance-to-go
Reaction:
Correction block is reorganized.
Interface signals are set.
Alarm display.
Remedy:
Include a probe number within the limits given above in the keyword MEAW=... This must correspond
to the hardware connection of the probe.
Program
Continuation:
Clear alarm with NC START or RESET key and continue the program.
15950
Channel %1 block %2 no traverse motion programmed
Parameters:
%1 = Channel number
%2 = Block number, label
Definitions:
Measure with deletion of distance-to-go
In the part program, no axis or a traversing path of zero has been programmed with the command
MEAS (measure with deletion of distance-to-go).
Reaction:
Correction block is reorganized.
Interface signals are set.
Alarm display.
Remedy:
Correct the part program and add the axis address or the traversing path to the measurements block.
Program
Continuation:
Clear alarm with NC START or RESET key and continue the program.
15960
Channel %1 block %2 no traverse motion programmed
Parameters:
%1 = Channel number
%2 = Block number, label
Definitions:
Measure without deletion of distance-to-go
In the part program, no axis or a traversing path of zero has been programmed with the command
MEAW (measure without deletion of distance-to-go).
Reaction:
Correction block is reorganized.
Interface signals are set.
Alarm display.
Remedy:
Correct the part program and add the axis address or the traversing path to the measurements block.
Program
Continuation:
Clear alarm with NC START or RESET key and continue the program.