NCK alarms
11/2006
Overview of Alarms
2-549
©
Siemens AG, 2006. All rights reserved
SINUMERIK, SIMODRIVE Diagnostics Manual (DA), 11/2006 Edition
61417
Channel %1 block %2: Probe will collide with the carrier of the reference
groove.
Parameters:
%1 = Channel number
%2 = Block number, label channel number
Definitions:
The alarm can be triggered by the following measuring cycles: CYCLE973
Remedy:
Take up collision-free initial position of the axes involved in the measuring process.
61418
Channel %1 block %2: Protocol file too small, check MD11420:
LEN_PROTOCOL_FILE.
Parameters:
%1 = Channel number
%2 = Block number, label channel number
Definitions:
Alarm can be triggered by following measuring cycle: CYCLE106
Remedy:
Check MD11420: LEN_PROTOCOL_FILE.
61419
Channel %1 block %2: Check probe calibration with reference to center
of ball/circumference of ball.
Parameters:
%1 = Channel number
%2 = Block number, label channel number
Definitions:
The alarm can be triggered by the following measuring cycles: CYCLE974, CYCLE994, CYCLE977,
CYCLE978, CYCLE979, CYCLE997, CYCLE998
Remedy:
The workpiece probe must be calibrated according to its use in the measuring cycles.
61420
Channel %1 block %2: Check calibration of multi/mono probes.
Parameters:
%1 = Channel number
%2 = Block number, label channel number
Definitions:
The alarm can be triggered by the following measuring cycles: CYCLE974, CYCLE994, CYCLE977,
CYCLE978, CYCLE979, CYCLE997, CYCLE998
Remedy:
The workpiece probe must be calibrated according to its type and use.
61421
Channel %1 block %2: Software release of measuring cycles or NCK
inadequate or set up incorrectly --> error code %4
Parameters:
%1 = Channel number
%2 = Block number, label channel number
Definitions:
The alarm can be triggered by the following measuring cycles: CYCLE996
Remedy:
Causes of error:
1. Error code = A -> _OVR[] - parameter field too small. Check GUD definition.
DEF CHAN REAL _OVR[72] (up to MZ06.03.xx.xx =32)
61422
Channel %1 block %2: Parameter _MVAR incorrect --> Error code: %4
Parameters:
%1 = Channel number
%2 = Block number, label channel number
Definitions:
The alarm can be triggered by the following measuring cycles: CYCLE996
Remedy:
Causes of error:
1. Error code = A -> _MVAR = 9x identifier CYCLE996 measure kinematics
2. Error code = B -> Parameter for normalizing (_MVAR) incorrect
3. Error code = C -> Measurement variant "compute only" active, but rotary axis 1 or 2 not
measured
(see also parameter _OVR[40])