NCK alarms
11/2006
Overview of Alarms
2-103
©
Siemens AG, 2006. All rights reserved
SINUMERIK, SIMODRIVE Diagnostics Manual (DA), 11/2006 Edition
10253
[up to SW 3.x only] Channel %1 reorg sequence canceled
Parameters:
%1 = Channel number
Definitions:
Internal sequence error. REORG is not possible at present.
Reaction:
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy:
Press RESET.
Program
Continuation:
Clear alarm with the RESET key. Restart part program
10254
[up to SW 3.x only] Channel %1 reorg sequence canceled
Parameters:
%1 = Channel number
Definitions:
Interpreter output negative acknowledgement for REORG.
Reaction:
Channel not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy:
Press RESET.
Program
Continuation:
Clear alarm with the RESET key. Restart part program
10255
[up to SW 3.x only] Channel %1 reorg sequence canceled
Parameters:
%1 = Channel number
Definitions:
Internal sequence error. REORG is not possible at present.
Reaction:
Channel not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy:
Press RESET.
Program
Continuation:
Clear alarm with the RESET key. Restart part program
10256
[up to SW 3.x only] Channel %1 reorg sequence canceled
Parameters:
%1 = Channel number
Definitions:
Internal sequence error. REORG is not possible at present - program abort.
Reaction:
Channel not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy:
Press RESET.
Program
Continuation:
Clear alarm with the RESET key. Restart part program